Falcon XG1.5K-1T, XG2.2K-1T, XG3K-1T manual Testing NEW Batteries, Recycling the Used Battery

Page 24

Extended Battery Modules Replacement

1.Unplug the connected battery cable from UPS and battery module.

2.Loosen and remove the screws from front panels. Remove both front panels from the module as shown above.

3.Lay the panels and screws aside for reassembly.

4.Loosen and remove the screws of battery stoppers. Lay them aside for reassembly.

5.Grasp the battery pack, and pull it out of the front of each module. Mark the top of each pack.

6.Unpack the new battery packs. Taking care not to destroy the packing. Compare new and old battery packs to verify they are same. If so, proceed with next the STEP, otherwise STOP and contact Falcon Service.

7.Line up and slide in the new replacement battery packs with right polarity by verifying against the marked battery pack.

8.Reinstall the battery stoppers with the screws.

9.Reinstall panels to the unit with the screws.

10.Connect the cable to the battery connector of UPS and that of the module.

TESTING NEW BATTERIES

Press the “FUNCTION/TEST” button for three seconds to initiate the battery test. If the UPS goes to ON-LINE MODE for over 10 seconds, it means the battery is good. If it does not, first check the connected battery cable and the battery connections. Otherwise, call Falcon Service if the problem persists.

RECYCLING THE USED BATTERY

Do not discard the UPS, the UPS battery pack, or batteries in the trash. Contact your local recycling or hazardous waster center for information on proper disposal of the used battery pack and batteries.

NEVER dispose of batteries in a fire, as batteries will explode.

24

Image 24
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonNormal ON-LINE Mode Battery ModeOperation Operating ModesBypass Mode Green ModeTurning the UPS on UPS Setup Configuration How To Place The UPS Into Setup/CONFIGURATION ModeGreen Mode Function BIT Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardMaintenance UPS and Battery CareWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSDimensions WeightInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions