Falcon XG2.2K-1T Inspecting the Equipment, RACK-MOUNT UPS Setup, FREE-STANDING UPS Installation

Page 7

XG1.5K-1T

XG2.2K-1T / XG3K-1T

1 box contains:

2 boxes contain:

 

Box 1:

UPS module with fitted battery pack

UPS module without battery

RS-232 cable

RS-232 Cable

Software CD

Software CD

Manual

Manual

19” rack ears (+ screws)

19” rack ears (+ screws)

Tower Mounting feet

Tower Mounting feet

 

Box 2:

 

Battery Module

 

Battery connection cable

 

Keyhole hardware

 

19” rack ears (+ screws)

 

1 set of mounting plates

INSPECTING THE EQUIPMENT

 

Visually inspect the UPS for freight damage. If any equipment has been damaged during shipment, keep the shipping cartons and packing materials for the carrier, and immediately file a claim for shipping damage with the carrier. If you discover damage after acceptance, file a claim for concealed damage.

To file a claim for shipping damage or concealed damage:

1.YOU MUST file with the carrier within 15 days of receipt of the equipment;

2.YOU MUST send a copy of the damage claim within 15 days to Falcon Electric, Inc.

CAUTION

The UPS and Battery Module are heavy. Take proper precautions when lifting or moving them.

Install the UPS indoors in a controlled environment; place it in an area with unrestricted airflow around the unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants. Maintain a minimum clearance of 4 inches in the front and rear of the UPS. Maintain an ambient temperature range of 32oF to 104oF (0oC to 40oC). To maximize the life time of the batteries, an ambient temperature of 68oF to 77oF (20oC to 25oC) is recommended. OPERATION IN TEMPERATURES ABOVE 77OF (25OC) WILL REDUCE BATTERY LIFE.

The XG Series UPS can be installed in either a free-standing mini-tower or into a 19 inch equipment rack. Follow the appropriate instructions in either RACK-MOUNT UPS SETUP or

FREE-STANDING UPS INSTALLATION.

RACK-MOUNT UPS SETUP

All XP Series UPSs are shipped with front panel mounting ears that allows the unit to be installed in a 19” rack. Each UPS unit and external battery enclosure needs 2U of rack space.

7

Image 7
Contents Owners Operating Manual Table of Contents Battery InstallationStorage and Transportation Introduction Circuit Descriptions Block DiagramInstallation FREE-STANDING UPS Installation RACK-MOUNT UPS SetupInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation Display & Controls SET/ALARM Silence BypassFUNCTION/TEST Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsOperating Modes Normal ON-LINE ModeBattery Mode OperationGreen Mode Bypass ModeTurning the UPS on Turning the UPS OFF UPS Setup ConfigurationHow To Place The UPS Into Setup/CONFIGURATION Mode Green Mode Function BITHow to Set the UPS Output Voltage How to Enable or Disable Green ModeConfiguration Mode Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleBattery Pack Replacement MaintenanceUPS and Battery Care When to Replace BatteriesInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideInput DimensionsWeight Internal Battery PackModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty