Falcon XG3K-1T, XG1.5K-1T, XG2.2K-1T manual Block Diagram, Circuit Descriptions

Page 5

BLOCK DIAGRAM

2.0 CIRCUIT DESCRIPTIONS

INPUT FILTER

This internal UPS circuit provides surge protection, certified to meet IEC 61000-4-5 and IEC 801-5. It also filters both electro-magnetic interference (EMI) and radio frequency interference (RFI). It minimizes surges or RFI interference present on the utility line.

CURRENT AND POWER FACTOR REGULATOR

In normal operation, this circuit converters utility AC power to regulated DC power for inverter use. It ensures the input current maintains a sine waveform to minimize the amount of current distortion that will be reflected to the utility. The XG Series UPS can tolerate a wide input range and has an overload power factor regulator alarm to alert the user in the event the UPS has an excessively heavy output load, while operation from a utility source with abnormally low input voltage.

DC/DC CONVERTER

The DC/DC converter utilizes energy from battery and boosts up the DC bus voltage to a level required by the inverter. This allows the inverter to operate continuously at optimum efficiency and voltage. The converter has a patented circuit which reduces the amount of ripple current and EMI interference to the battery.

DC/AC INVERTER

In normal on-line operation, the Inverter utilizes the regulated DC output to invert DC back into clean, regulated sinewave AC power. When utility power fails, the inverter will receive its energy from the battery through the DC/DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating clean, regulated AC output power to the load. The XG Series has a pure sinewave output, which is produced with a Pulse Width Modulation (PWM) Inverter. As a result, the UPS output is very stable, even with nonlinear loads.

5

Image 5
Contents Owners Operating Manual Table of Contents Storage and Transportation InstallationBattery Introduction Circuit Descriptions Block DiagramInstallation Inspecting the Equipment RACK-MOUNT UPS SetupFREE-STANDING UPS Installation Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation FUNCTION/TEST SET/ALARM Silence BypassDisplay & Controls Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsBattery Mode Normal ON-LINE ModeOperation Operating ModesTurning the UPS on Bypass ModeGreen Mode How To Place The UPS Into Setup/CONFIGURATION Mode UPS Setup ConfigurationGreen Mode Function BIT Turning the UPS OFFConfiguration Mode How to Enable or Disable Green ModeHow to Set the UPS Output Voltage Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleUPS and Battery Care MaintenanceWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideWeight DimensionsInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty