Falcon XG1.5K-1T Standard Dry Contact Interface Card Novell style, UA88374 Relay Option Board

Page 21

Standard Dry Contact Interface Card (Novell style)

Please refer to the following schematic for interface details:

DB-9

JP1

J1

JP2

J2

JP3

J3

 

 

PIN & JUMPER ASSIGNMENT FOR THE FALCON

 

 

UA88374 RELAY OPTION BOARD

 

 

(no on-bypass signal)

 

PIN

DESCRIPTION

 

 

1

Low Battery ( When UPS reaches low battery, contact activates)

 

 

 

(J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

 

 

2

JP2 shorted = Low Battery common & all other shorted JP commons

 

 

 

JP2 open = common for low battery only

 

 

3

Utility Loss N.O. ( At loss of utility voltage, contact activates)

 

 

4

Utility Loss N.C. ( At loss of utility voltage, contact activates)

 

 

5

JP1 shorted = Utility Loss common & all other shorted JP commons

 

 

 

JP1 open = Utility Loss common only

 

 

6

Remote Shutdown common

 

 

7

Remote Shutdown

 

 

 

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

 

 

 

1-2 shorted. Applying an external 12V signal across the DB-9, pins six

 

 

 

and seven, while the UPS is on battery, will turn the UPS off.

 

 

 

2-3 shorted. Applying a short directly across the DB-9, pins six and

 

 

 

seven, while the UPS is on battery, will turn the UPS off.

 

 

8

Alarm (Upon a UPS fault or failure the contact activates)

 

 

 

(J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

 

 

9

JP3 shorted = Alarm common & all other shorted JP commons

 

 

 

JP3 open = Alarm common only

 

 

 

PIN & JUMPER ASSIGNMENT FOR THE FALCON

 

 

UA88376 RELAY OPTION BOARD

 

 

(with on-bypass signal)

 

 

 

 

 

DB-9F PIN & JUMPER ASSIGNMENTS

 

PIN

DESCRIPTION

 

1

Low Battery ( When UPS reaches low battery, contact activates)

 

 

(J1, 1-2 short = N.O) (J1, 2-3 short = N.C)

 

2

JP2 shorted = Low Battery common & all other shorted JP commons

 

 

JP2 open = common for low battery only

 

3

Utility Loss N.O. ( At loss of utility voltage, contact activates)

 

4

Utility Loss N.C. ( At loss of utility voltage, contact activates)

 

5

JP1 shorted = Utility Loss common & all other shorted JP commons

 

 

JP1 open = Utility Loss common only

 

6

Remote Shutdown common

 

7

Remote Shutdown

 

 

(J2, 1-2 short = outside power) (J2, 2-3 short = inside power)

 

 

1-2 shorted. Applying an external 12V signal across the DB-9, pins six

 

 

and seven, while the UPS is on battery, will turn the UPS off.

 

 

2-3 shorted. Applying a short directly across the DB-9, pins six and

 

 

seven, while the UPS is on battery, will turn the UPS off.

 

8

On Bypass or Alarm (Upon the UPS going to bypass or a UPS failure

 

 

the contact activates)

 

 

(J3, 1-2 short = N.O.) (J3, 2-3 short = N.C.)

 

9

JP3 shorted = On bypass, Alarm common & all other shorted JP

 

 

commons

 

 

JP3 open = On bypass, Alarm common only

21

Image 21
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Circuit Descriptions Block DiagramInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsBattery Mode Normal ON-LINE ModeOperation Operating ModesBypass Mode Green ModeTurning the UPS on How To Place The UPS Into Setup/CONFIGURATION Mode UPS Setup ConfigurationGreen Mode Function BIT Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleUPS and Battery Care MaintenanceWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideWeight DimensionsInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty