Falcon XG3K-1T, XG1.5K-1T manual Model Number XG2.2K-1T

Page 29

Model Number

XG2.2K-1T

 

 

XG3K-1T

Model Rating

2200VA/1540W

 

 

3000VA/2100W

DIMENSIONS

 

 

 

 

Unit

 

16.8 x 21.5 x 3.5 (2U)

 

 

16.8 x 21.5 x 3.5 (2U)

W x D x H in. (mm)

(426 x 546 x88)

 

 

(426 x 546 x 88)

Shipping

 

22 x 25.75 x 8.5

 

 

22 x 25.75 x 8.5

W x D x H in. (mm)

(560 x 654 x 215)

 

 

(560 x 654 x 215)

WEIGHT

 

 

 

 

 

Unit

lbs (kg)

63.9 (29)

 

 

66.2 (30)

Shipping

lbs (kg)

87.1 (39.5)

 

 

89.3 (40.5)

INPUT

 

 

 

 

 

Voltage Range

120 VAC nominal; variable based on output load

 

 

80 – 138 VAC full load,

 

 

 

60 – 138 VAC 25% load, without using battery

Frequency

45 – 65 Hz auto sensing

 

Power Factor

>0.98 at full load

 

Current Harmonics

< 9% at full load

 

Protection

Fuse

 

Power Cord

6 ft. attached with

 

6 ft. attached with

 

 

NEMA L5-20 plug

 

NEMA L5-30 plug

OUTPUT

 

 

 

 

 

Output Receptacles

(4) NEMA 5-15R

 

(4) NEMA 5-15R or

 

 

(1) L5-30R & 1) 5-15

 

(1) L5-30R & 1) 5-15R

Voltage

 

100/110/115/120 (user

configurable) VAC

Voltage Regulation

+ 2% of nominal

Frequency

60 Hz

Waveform/Distortion

Sinewave/ THD < 3% @ full linear load

Overload

 

100~110% for 120 seconds,

 

 

 

111~150% for 20 seconds,

 

 

 

151% immediately, transfer to bypass within 4 ms

Short Circuit Protection

15A Fuse for per 2 output outlets

BATTERY MODULE ( 1each Standard with 2.2 & 3kVA UPS)

Back-up time

See Battery Run Time charts

DIMENSIONS

 

 

 

 

Unit

 

16.8 x 21.5 x 3.5

W x D x H in. (mm)

(426 x 546 x 88.9)

Shipping

 

25.75 x 21.5 x 8.5

W x D x H in. (mm)

(654 x 546 x 215)

WEIGHT

 

 

 

 

 

Unit

lbs (kg)

62 (28)

Shipping

lbs (kg)

78 (35.3)

Packs

 

2 x 48 VDC packs per module (2)( PN BA04009

Battery Type

Sealed Lead Acid, Valve-regulated, Rechargeable

 

 

29

 

 

 

Image 29
Contents Owners Operating Manual Table of Contents Storage and Transportation InstallationBattery Introduction Circuit Descriptions Block DiagramInstallation Inspecting the Equipment RACK-MOUNT UPS SetupFREE-STANDING UPS Installation Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation FUNCTION/TEST SET/ALARM Silence BypassDisplay & Controls Indicators and Icons Located on the LCD Display FUNCTION/TEST Button ControlsBattery Mode Normal ON-LINE ModeOperation Operating ModesTurning the UPS on Bypass ModeGreen Mode How To Place The UPS Into Setup/CONFIGURATION Mode UPS Setup ConfigurationGreen Mode Function BIT Turning the UPS OFFConfiguration Mode How to Enable or Disable Green ModeHow to Set the UPS Output Voltage Communications An Example of How to Set the UPS Output Voltage to 115VacPIN # RS-232 PortUA88374 Relay Option Board Standard Dry Contact Interface Card Novell styleUPS and Battery Care MaintenanceWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Recycling the Used Battery Testing NEW BatteriesFuse Replacement Troubleshooting Guide TroubleshootingUPS Troubleshooting GuideWeight DimensionsInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times General Provisions Warranty