Falcon XG3K-1T, XG1.5K-1T, XG2.2K-1T manual RS-232 Port, Pin #

Page 20

Note: A special external SNMP/HTTP Agent device is available that connects to the UPS’s RS-232 Port. This allows for one Dry Contact interface board to be installed into the Advanced Communications Option Slot concurrently.

CAUTION: When an internal SNMP/HTTP AGENT device is installed into the Advanced Communications Option Slot, the RS-232 port and UPSILON software may not be used.

The RS-232 PORT

The unit is equipped with one RS-232 port located on the UPS rear panel. A SPECIAL interface cable is provided to allow for the connection of the UPS to another RS-232 port found on most computers. When this cable has been connected, and the supplied UPSILON Computer Shutdown and Management software has been properly installed on the connected computer, a high level of protection against lost or corrupted files is in effect.

Please refer to the UPSILON Users Manual located on the UPSILON CD supplied with this unit. UPSILON supports most popular operating systems. Should you have special UNIX requirements, please contact Falcon Electric

The UPS & PC Computer DB-9 pin designations are as follows:

PIN #

PIN Definition (UPS)

PIN Definition (PC)

2

Transmitted data

Received data

3

Received data

Transmitted data

4

DTE Ready

DTE Ready

5

Signal Ground

Signal Ground

The supplied Falcon interface cable pin designations are as follows:

The computer RS-232 Port settings should be set to the following:

Baud Rate

2400 bps

Data Length

8 bits

Stop Bit

1 bit

Parity

None

 

20

Image 20
Contents Owners Operating Manual Table of Contents Storage and Transportation InstallationBattery Introduction Block Diagram Circuit DescriptionsInstallation Inspecting the Equipment RACK-MOUNT UPS SetupFREE-STANDING UPS Installation Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation FUNCTION/TEST SET/ALARM Silence BypassDisplay & Controls Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonNormal ON-LINE Mode Battery ModeOperation Operating ModesTurning the UPS on Bypass ModeGreen Mode UPS Setup Configuration How To Place The UPS Into Setup/CONFIGURATION ModeGreen Mode Function BIT Turning the UPS OFFConfiguration Mode How to Enable or Disable Green ModeHow to Set the UPS Output Voltage An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardMaintenance UPS and Battery CareWhen to Replace Batteries Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSDimensions WeightInternal Battery Pack InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions