Falcon XG1.5K-1T, XG2.2K-1T, XG3K-1T manual Installation

Page 6

BATTERY

The XG Series UPS utilizes a flame retardant battery pack comprised of four 12V 7 AH, valve- regulated, and sealed lead acid batteries. All XG battery packs are interchangeable. They are easy to install or change. To maintain battery design life, the user should operate the UPS in an ambient temperature of 68oF to 77oF (20oC to 25oC). Extended Battery modules are available to provide extend battery run times.

CHARGER

The battery charger uses the energy from the utility power to continuously charge the UPS batteries. The charger operates in “constant power” mode. The UPS batteries are being charged whenever the UPS is plugged in. The charger will continue to operate as long as the utility voltage is over 60 Vac.

BYPASS TRANSFER SWITCH

The XG Series UPS automatically switches to bypass to energize the connected load when UPS encounters an overload, over temperature, over input current, over crest-factor load (designed for 3:1 nonlinear load), or a UPS failure condition. Should any of these events occur, the UPS will automatically transfer to bypass mode with an audible alarm, and provide a “bypass” indication on the LCD display.

OUTPUT FILTER

This filter prevents electro-magnetic conductance (EMC) leakage and RFI noise to the UPS output.

3. 0 INSTALLATION

UNPACKING

The XG Series UPS may be shipped in a number of boxes, depending on the model and configuration ordered. The number of boxes you have received should be as indicated:

MODEL

BATTERY MODULE

NUMBER OF BOXES

XG1.5K-1T

n/a (internal battery pack)

1 box shipped

XG2.2K-1T

1 battery module

2 boxes shipped

XG3K-1T

1 battery module

2 boxes shipped

If you have not received the proper number of boxes, please contact Falcon Electric Customer Service at 1-800-842-6940

This UPS is shipped complete with all cables required for operation, along with UPSILON software, and rackmount ears for 19” shelf mounting. A full list of the box contents is provided as follows:

6

Image 6
Contents Owners Operating Manual Table of Contents Installation BatteryStorage and Transportation Introduction Block Diagram Circuit DescriptionsInstallation RACK-MOUNT UPS Setup FREE-STANDING UPS InstallationInspecting the Equipment Page FREE-STANDING UPS Installation Mounting feet Mounting feet for additional Battery Modules Battery Module Installation SET/ALARM Silence Bypass Display & ControlsFUNCTION/TEST Indicators and Icons Located on the LCD Display Controls FUNCTION/TEST ButtonOperation Normal ON-LINE ModeBattery Mode Operating ModesBypass Mode Green ModeTurning the UPS on Green Mode Function BIT UPS Setup ConfigurationHow To Place The UPS Into Setup/CONFIGURATION Mode Turning the UPS OFFHow to Enable or Disable Green Mode How to Set the UPS Output VoltageConfiguration Mode An Example of How to Set the UPS Output Voltage to 115Vac CommunicationsRS-232 Port PIN #Standard Dry Contact Interface Card Novell style UA88374 Relay Option BoardWhen to Replace Batteries MaintenanceUPS and Battery Care Battery Pack ReplacementInternal Battery Pack Replacement Testing NEW Batteries Recycling the Used BatteryFuse Replacement Troubleshooting Troubleshooting GuideTroubleshooting Guide UPSInternal Battery Pack DimensionsWeight InputModel Number XG2.2K-1T Battery RUN Times Warranty General Provisions