Briggs & Stratton 01928-1, 01814-1, 01929-1, 01813-1 manual Troubleshooting, Problem Cause Correction

Page 12

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Operator’s Manual

TROUBLESHOOTING

Problem

Cause

Correction

Automatic transfer switch does

1.

Generator breaker open.

1.

Reset generator circuit breaker.

not transfer to generator

2.

Generator voltage not acceptable.

2.

Refer to generator manual.

 

 

 

 

 

 

1.

Utility disconnect breaker open

1.

Reset utility disconnect breaker

Automatic transfer switch does

 

(Models 01928-1 & 01929-1 only).

 

(Models 01928-1 & 01929-1 only).

2.

Service disconnect breaker open.

2.

Reset service disconnect breaker.

not transfer to utility

3.

Utility voltage not acceptable.

3.

Wait for utility voltage to return to

 

 

 

 

 

normal.

 

 

 

Generator is still running after

Engine cool down period.

Engine should stop after 1 minute.

switch transfers to utility power

 

 

 

 

 

 

 

Supervised loads (air conditioner,

NC contacts not operating correctly.

Check NC contacts for proper

etc.) are operating when

 

 

operation and/or check control wiring

generator is supplying power

 

 

to external load.

 

 

 

 

 

 

1.

Minimum engine run time has not

1.

Wait five minutes for transfer

Generator is still running after

 

elapsed.

 

switch to retransfer to utility

 

 

 

power.

utility power is restored

 

 

 

2.

Fuse(s) in transfer switch is

2.

Check fuse(s) and replace if

 

 

 

defective.

 

necessary.

 

 

 

 

 

12

Image 12
Contents Amp / 200 Amp Table of Contents Important Safety Instructions Only qualified electricians should attempt installationUse transfer switch only for intended uses Introduction For the Home OwnerOwner Orientation Installation Shipment ContentsDelivery Inspection Typical Transfer Switch Mounting for Models 01928-1 Power Wiring Interconnections Typical Installation Diagram for Transfer Switch Testing the Automatic Transfer Switch System OperationSpecifications UL 1008 Listed Transfer Switch ModelFault Current Rating ,000 RMS Symmetrical Amperes Troubleshooting Problem Cause CorrectionInstallation and Operator’s Manual Transfer Switch Schematic Models 01813-1Transfer Switch Wiring Diagram Models 01928-1Transfer Switch Exploded View & Parts List DescriptionItems without part numbers are common fasteners DECAL, 200A,ATS LOCKWASHER, #10 BUS BAR Installation and Operator’s Manual Limited Warranty Guide dinstallation et dutilisation Table DES MatièresAvertissement Au Détaillant ou à lEntrepreneur Procédant à lInstallation IntroductionAu Propriétaire Résidentiel Responsabilités de lInstallateur Conseils au PropriétaireDescription de lÉquipement Installation Consignes dinstallationDéballage Vérification de la LivraisonUne installation alternative du commutateur de transfert Interconnexions du Câblage dAlimentation Câblage de contrôleSchéma dInstallation Typique du Commutateur de Transfert Fonctionnement Mise À Lessai DU Commutateur DE Transfert AutomatiqueSéquence Automatique Si vous Devez Communiquer avec lUsineCaractéristiques UL 1008 Enuméré Commutateur de Transfert ModéleCharge maximum/circuit Valeur nominale desDépannage Garantie Limitée Tabla DE Contenido Manual de Instalación y del OperarioAdvertencia PrecauciónIntroducción Para el Propietario DomésticoOrientación para el Propietario Responsabilidades del InstaladorDescripción del Equipo Lea y cumpla las instrucciones incluidas en el manualInstalación DesempaquePautas de Montaje Inspección al Momento de la EntregaFigura 13 Montaje de un Conectador Alternativo Interconexiones de Cableado de Energía Cableado de Control de SupervisiónContactor del Acondicionador de aire Alimentación Neutro Figura 11 Un Esquema Típico de Instalación para Conectador Sistema Funcionamiento Prueba DEL Conectador AutomáticoSecuencia Automática Si Necesita Llamar a FábricaProblemo Causa Accion EspecificacionesReparacion DE Averias Garantía Limitada