Briggs & Stratton 01928-1, 01814-1, 01929-1, 01813-1 manual Power Wiring Interconnections

Page 8

Briggs & Stratton Power Products Automatic Transfer Switch

Installation and Operator’s Manual

Power Wiring Interconnections

All wiring must be the proper size, properly supported and protected by conduit.

Complete the following connections between the transfer switch, main distribution panel, utility power and generator (Figure 4, on next page).

WARNING

Low voltage wire cannot be installed in same conduit as power voltage wiring.

Failure to follow above warning could cause personal injury, damage and/or malfunction of equipment.

1.Ensure utility power is turned OFF. Connect utility power supply leads to transfer switch terminals marked “UTILITY CONNECTION”.

2.Connect utility neutral to the transfer switch “NEUTRAL” terminal.

3.Connect main distribution panel power leads to transfer switch terminals marked “LOAD CONNECTION”.

4.Connect main distribution panel neutral lead to transfer switch “NEUTRAL” terminal.

5.Connect generator power supply leads from the generator’s control panel to transfer switch terminals marked “GENERATOR CONNECTION”.

6.Connect generator Neutral from the control panel to the transfer switch “NEUTRAL” terminal.

7.Connect generator “GND” from the control panel to the transfer switch “GND” terminal.

8.Connect main distribution panel “GND” to the transfer switch “GND” terminal.

NOTE: Assure grounding electrode conductor is connected and bonded per applicable federal, state and local codes, standards and regulations.

9.Connect generator utility 240 VAC terminals to transfer switch utility 240 VAC terminals.

10.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

Supervisory Control Wiring

Terminal strip on control module in transfer switch has four connections for customer use.There are two sets of “Normally Closed” contacts available.They will be opened when generator power is required.These can be used to lock out large loads when powered by generator. Example: air conditioner, hot water heater, etc..

1.Terminals on control module are for installer supplied contactors to lock out large loads. Example: air conditioner, electric hot water heater, etc.. Contacts are connected in series with the contactor control circuit (Figure 5).

Figure 5 — Terminals on Control Module

Air Conditioner Contactor

Supply

Contactor

Neutral

120 VAC

2.Tighten all wire connections/fasteners to proper torque. See inside transfer switch enclosure for proper torque values.

8

Image 8
Contents Amp / 200 Amp Table of Contents Use transfer switch only for intended uses Important Safety InstructionsOnly qualified electricians should attempt installation Introduction For the Home OwnerOwner Orientation Delivery Inspection InstallationShipment Contents Typical Transfer Switch Mounting for Models 01928-1 Power Wiring Interconnections Typical Installation Diagram for Transfer Switch Testing the Automatic Transfer Switch System OperationFault Current Rating ,000 RMS Symmetrical Amperes SpecificationsUL 1008 Listed Transfer Switch Model Troubleshooting Problem Cause CorrectionInstallation and Operator’s Manual Transfer Switch Schematic Models 01813-1Transfer Switch Wiring Diagram Models 01928-1Items without part numbers are common fasteners Transfer Switch Exploded View & Parts ListDescription DECAL, 200A,ATS LOCKWASHER, #10 BUS BAR Installation and Operator’s Manual Limited Warranty Guide dinstallation et dutilisation Table DES MatièresAvertissement Au Propriétaire Résidentiel Au Détaillant ou à lEntrepreneur Procédant à lInstallationIntroduction Description de lÉquipement Responsabilités de lInstallateurConseils au Propriétaire Installation Consignes dinstallationDéballage Vérification de la LivraisonUne installation alternative du commutateur de transfert Interconnexions du Câblage dAlimentation Câblage de contrôleSchéma dInstallation Typique du Commutateur de Transfert Fonctionnement Mise À Lessai DU Commutateur DE Transfert AutomatiqueSéquence Automatique Si vous Devez Communiquer avec lUsineCaractéristiques UL 1008 Enuméré Commutateur de Transfert ModéleCharge maximum/circuit Valeur nominale desDépannage Garantie Limitée Tabla DE Contenido Manual de Instalación y del OperarioAdvertencia PrecauciónIntroducción Para el Propietario DomésticoOrientación para el Propietario Responsabilidades del InstaladorDescripción del Equipo Lea y cumpla las instrucciones incluidas en el manualInstalación DesempaquePautas de Montaje Inspección al Momento de la EntregaFigura 13 Montaje de un Conectador Alternativo Contactor del Acondicionador de aire Alimentación Neutro Interconexiones de Cableado de EnergíaCableado de Control de Supervisión Figura 11 Un Esquema Típico de Instalación para Conectador Sistema Funcionamiento Prueba DEL Conectador AutomáticoSecuencia Automática Si Necesita Llamar a FábricaReparacion DE Averias Problemo Causa AccionEspecificaciones Garantía Limitada