MGE UPS Systems 40-150kVA AC Input Ratings, Voltage, Frequency, Phases, Wires, Power factor

Page 21

Installation and User Manual

NOTES:

1.Total width, weight, and heat loss are for system line-up excluding battery cabinets.

2.Data does not include battery data; refer to the installation drawings supplied with your equipment. Consult the installation drawings provided with your equipment.

1.3.1AC Input Ratings

Voltage

 

480 VAC, + 12%, -15%

 

 

 

 

Frequency

 

60 Hz ± 4%

 

 

 

 

Phases

 

3 Ø (phase sequence must be A, B, C, clockwise)

 

 

Wires

 

3 wires plus ground (480-480 VAC only)

 

 

 

Power factor

Approximately 0.98 at full load

 

 

 

Current (on UPS/ on BYPASS) @ 480 VAC

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

43A/48A

54A/60A

70A/78A

86A/96A

109A/120A

134A/150A

160A/180A

1.3.2AC Output Ratings

Voltage (inverter only)

480 ± 1% VAC (steady-state conditions)

 

 

 

 

480 ± 5% VAC (transient conditions from 0% to 100% or 100% to 0%)

Frequency

 

60 Hz ± 0.1% (free-running)

 

 

 

Phases

 

3 Ø (phase sequence must be A, B, C, clockwise)

 

Wires

 

3 wires plus ground (480-480 VAC only)

 

 

Power factor

0.8

 

 

 

 

Current @ 480 VAC

 

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

48A

60A

78A

96A

120A

150A

180A

Total harmonic

 

 

 

 

 

distortion (THD)

<2% (linear load)

 

 

 

 

 

<3% (for 100% non-linear load with a crest factor of less than 3.0)

Dynamic regulation

± 1% for balanced load

 

 

 

 

 

± 2.5% for 100% unbalanced load

 

 

Dynamic response

± 5% for 100% step load change

 

 

Overload

 

105% - 110% of rated current for 10 minutes

 

 

 

 

>110% - 130% of rated current for 1 minute

 

 

 

 

>130% - 150% of rated current for 10 seconds

 

 

 

>150% of rated current for 0.15 seconds

 

 

1.3.3DC Ratings

Battery voltage (25° C)

float:

 

490 Vdc

 

 

 

 

nominal:

432 Vdc

 

 

 

 

minimum:

360 Vdc

 

 

Maximum Current at cut-off voltage

 

 

 

 

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

96 ADC

120 ADC

154 ADC

189 ADC

235 ADC

294 ADC

353 ADC

86-160310-00 E00

System Description and Specifications

1 — 9

Image 21
Contents Comet 40-150kVA Page Revision History CometComet 40-150kVA Important Safety InstructionsSafety of Persons Certification Standards Three Phase UPSProduct Safety Special PrecautionsThis page left blank intentionally Contents Operation MaintenanceWarranty and Product Registration MGE Warranty & Proprietary Rights for Three Phase ProductsCustomer Care Center Three Phase Products TablesUPS Serial Number Battery Serial Number This page left blank intentionally 86-160310-00 E00 Section Descriptions Comet 40-150kVA Symbol UsageSystem Description and Specifications ScopeGeneral Description Single Line Diagram for the Comet 40-80kVA Major Components Detail Behind Item Rear View of the Comet 40-80kVA FU1-FU21 Control Fuses TOP Conduit Landing for Cable Access to Pcas Specifications Wires PhasesPower factor DC Ratings Battery voltage 25 C6 DB15 Connector Pinouts and Designations Environmental Specifications TemperatureHumidity AltitudeOptions and Accessories Chaptername This page left blank intentionally Receiving InstallationHandling For assistanceStorage Prerequisite to InstallationMay adversely affect life EnvironmentalProper trip settings Short circuit when the unit is working on Static SwitchMechanical ElectricalConnections Installation ProceduresAC Output BatteryChaptername This page left blank intentionally Power Flow, For Normal Operation Power FlowPower Flow, For On Battery Operation OperationPower Flow, For Bypass Operation Graphical User Interface, Controls and IndicatorsComet Front Panel GUI, Controls and Indicators Fault LED Emergency Power OffBattery Status LED Fault ResetStartup Procedures Inverter Manual StartupPreliminary Checks Operation on Battery Power Operating ProceduresBattery Duration Return to AC PowerOutput Current Overload Curve Emergency Shutdown Using EPO/REPO Maintenance BypassForced Transfer Move the fan control switch SR2 to the OFF position Alarms Shutdown ProceduresPowering Down Inverter ShutdownMaintenance Battery SafetyPreventive Maintenance Level Description Replacement PartsApplicable within the United States, Canada and Mexico Warranty Extension Warranty+ User InformationProduct Information Technical Support and Product Services MGE Customer Care Center Three Phase ProductsScheduling Field Service Engineer Support Return Policy for Repair of Three Phase Products RGAComet 40-150kVA Term used Definition / Meaning GlossaryFCC NEC This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Page Page Contact MGE