Installation and User Manual
NOTES:
1.Total width, weight, and heat loss are for system
2.Data does not include battery data; refer to the installation drawings supplied with your equipment. Consult the installation drawings provided with your equipment.
1.3.1AC Input Ratings
Voltage |
| 480 VAC, + 12%, |
|
|
|
| |
Frequency |
| 60 Hz ± 4% |
|
|
|
| |
Phases |
| 3 Ø (phase sequence must be A, B, C, clockwise) |
|
| |||
Wires |
| 3 wires plus ground |
|
|
| ||
Power factor | Approximately 0.98 at full load |
|
|
| |||
Current (on UPS/ on BYPASS) @ 480 VAC |
|
|
|
| |||
40kVA | 50kVA | 65kVA | 80kVA | 100kVA | 125kVA | 150kVA | |
43A/48A | 54A/60A | 70A/78A | 86A/96A | 109A/120A | 134A/150A | 160A/180A |
1.3.2AC Output Ratings
Voltage (inverter only) | 480 ± 1% VAC |
|
| |||
|
| 480 ± 5% VAC (transient conditions from 0% to 100% or 100% to 0%) | ||||
Frequency |
| 60 Hz ± 0.1% |
|
|
| |
Phases |
| 3 Ø (phase sequence must be A, B, C, clockwise) |
| |||
Wires |
| 3 wires plus ground |
|
| ||
Power factor | 0.8 |
|
|
|
| |
Current @ 480 VAC |
|
|
|
|
| |
40kVA | 50kVA | 65kVA | 80kVA | 100kVA | 125kVA | 150kVA |
48A | 60A | 78A | 96A | 120A | 150A | 180A |
Total harmonic |
|
|
|
|
| |
distortion (THD) | <2% (linear load) |
|
|
| ||
|
| <3% (for 100% | ||||
Dynamic regulation | ± 1% for balanced load |
|
|
| ||
|
| ± 2.5% for 100% unbalanced load |
|
| ||
Dynamic response | ± 5% for 100% step load change |
|
| |||
Overload |
| 105% - 110% of rated current for 10 minutes |
|
| ||
|
| >110% - 130% of rated current for 1 minute |
|
| ||
|
| >130% - 150% of rated current for 10 seconds |
| |||
|
| >150% of rated current for 0.15 seconds |
|
|
1.3.3DC Ratings
Battery voltage (25° C) | float: |
| 490 Vdc |
|
| |
|
| nominal: | 432 Vdc |
|
| |
|
| minimum: | 360 Vdc |
|
| |
Maximum Current at |
|
|
|
| ||
40kVA | 50kVA | 65kVA | 80kVA | 100kVA | 125kVA | 150kVA |
96 ADC | 120 ADC | 154 ADC | 189 ADC | 235 ADC | 294 ADC | 353 ADC |
System Description and Specifications | 1 — 9 |