MGE UPS Systems 40-150kVA user manual Graphical User Interface, Controls and Indicators

Page 34

Comet 40-150kVA

3.1.3Power Flow, For Bypass Operation

Should there be an internal fault in the UPS, the load will automatically be transferred to the "Static Switch". (If bypass AC input is within tolerance). The load is supplied without interruption while the UPS is bypassed (see Figure 3-3).

Figure 3-3: Power Flow, For Bypass Operation.

STATIC SWITCH

BYPASS

INPUT

(OPTIONAL)

RECTIFIER

MAIN

INPUT

INVERTER

TO LOAD

BATTERY

3.2Graphical User Interface, Controls and Indicators

The Graphical User Interface (GUI) display, controls and indicators are located on the front panel in the upper left-hand corner of the Comet UPS, and consist of the following: (See Figure 3-4 for arrangement.)

A Graphical User Interface (GUI) display.

An alert buzzer.

Four (4) LED's which indicate the overall operating status of the UPS.

An “Inverter ON”, an “Inverter OFF”, and an “EPO” pushbutton.

Three (3) control keys.

The basic Comet indications consist of the following:

Normal operation (load protected)

Battery power is not available (load not protected)

Downgraded operation (fault)

Danger of a break in the supply of power to the load (load not protected)

Operation on battery power

When the buzzer is activated it will provide an audible warning to the operator by sounding a pulsed “beep” when any of the following conditions occur:

The load is supplied directly by AC input power via the "Static Switch".

The Inverter is operating on battery power.

Any operating faults or change in operating status.

It beeps softly and slowly for minor faults and during Inverter operation on battery power. When the low battery shutdown warning level has been reached, the sound volume and the frequency of the beeps increase.

In the event of an Inverter shutdown, a continuous alarm is emitted. A buzzer reset key is provided on the front panel. Detection of a new fault will reactivate the buzzer.

3 —2

Operation

86-160310-00 E00

Image 34
Contents Comet 40-150kVA Page Comet Revision HistoryImportant Safety Instructions Comet 40-150kVAProduct Safety Certification Standards Three Phase UPSSafety of Persons Special PrecautionsThis page left blank intentionally Contents Maintenance OperationCustomer Care Center Three Phase Products MGE Warranty & Proprietary Rights for Three Phase ProductsWarranty and Product Registration TablesUPS Serial Number Battery Serial Number This page left blank intentionally 86-160310-00 E00 Comet 40-150kVA Symbol Usage Section DescriptionsScope System Description and SpecificationsGeneral Description Single Line Diagram for the Comet 40-80kVA Major Components Detail Behind Item Rear View of the Comet 40-80kVA FU1-FU21 Control Fuses TOP Conduit Landing for Cable Access to Pcas Specifications Power factor PhasesWires DC Ratings Battery voltage 25 CHumidity Environmental Specifications Temperature6 DB15 Connector Pinouts and Designations AltitudeOptions and Accessories Chaptername This page left blank intentionally Handling InstallationReceiving For assistanceMay adversely affect life Prerequisite to InstallationStorage EnvironmentalMechanical Short circuit when the unit is working on Static SwitchProper trip settings ElectricalInstallation Procedures ConnectionsBattery AC OutputChaptername This page left blank intentionally Power Flow, For On Battery Operation Power FlowPower Flow, For Normal Operation OperationGraphical User Interface, Controls and Indicators Power Flow, For Bypass OperationComet Front Panel GUI, Controls and Indicators Battery Status LED Emergency Power OffFault LED Fault ResetInverter Manual Startup Startup ProceduresPreliminary Checks Battery Duration Operating ProceduresOperation on Battery Power Return to AC PowerOutput Current Overload Curve Maintenance Bypass Emergency Shutdown Using EPO/REPOForced Transfer Move the fan control switch SR2 to the OFF position Powering Down Shutdown ProceduresAlarms Inverter ShutdownBattery Safety MaintenancePreventive Maintenance Replacement Parts Level DescriptionApplicable within the United States, Canada and Mexico User Information Warranty Extension Warranty+Product Information Scheduling Field Service Engineer Support MGE Customer Care Center Three Phase ProductsTechnical Support and Product Services Return Policy for Repair of Three Phase Products RGAComet 40-150kVA Glossary Term used Definition / MeaningFCC NEC This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Page Page Contact MGE