Comet 40-150kVA
2.5Installation Procedures
The steps to be followed are:
◗Placement of the UPS and associated equipment.
◗Connection of input power, output power, and control cables.
Installation of UPS equipment must be handled by skilled technicians and electrician's familiar with the special requirements of
Refer to the installation drawings for proper placement and connections of auxiliary cabinets.
2.5.1Placement
Move the Comet UPS, battery cabinets (if any), and auxiliary cabinets (if any), to their final location (see Figure
Figure 2-2: Placement of UPS and other Cabinets.
AUX CAB
UPS
BATTERY CABINET(s)
For side and rear clearances, refer to each cabinet's installation drawing
36" recommended
2.6Connections
Electrical connections and cabinet interconnection will vary depending upon the configuration of your Comet UPS system. Refer to Figures
CAUTION | Before making any electrical connections, verify that all battery disconnect |
| circuit breaker (QF1) are in the “off” position. |
| protective devices and distribution circuits should be OFF. |
|
|
2.6.1Main AC Input
The connections to be made are the three phases, and ground cables from the utility AC power source to the UPS. The main AC input cables are terminated at the "Main Input" Terminal Block (TB1) for
2.6.2Bypass AC Input (Optional)
The connections to be made are the three phases, and ground cables from the bypass AC input power source to the UPS. The bypass AC input cables are terminated at the "Bypass Input" Terminal Block (TB3) for
2.6.3Remote Emergency Power Off (REPO)
The control connections are available for "Remote Emergency Power Off" (REPO) through a
2 — 4 | Installation |