MGE UPS Systems 40-150kVA Storage, Prerequisite to Installation, May adversely affect life

Page 27

Comet 40-150kVA

If the equipment is to be stored for more than three months before installation, it should be unpacked and connected to an AC input source to allow the batteries to be recharged. Refer to the installation instructions that follow, and the installation drawings.

Figure 2-1: The Comet 100-150kVA on Pallet.

2.3Storage

If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location that is protected against rain, splashing water, chemical agents, etc. The equipment should be covered with a tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.

IMPORTANT

Batteries should be stored no longer than three (3) months at approximately 25°C

 

(77° F) prior to recharging. Too high or too low a temperature will damage batteries.

 

Exceeding the recommended ambient storage temperature will reduce back-up time

 

and may adversely affect life.

 

 

 

2.4Prerequisite to Installation

This section provides more information for a successful and efficient installation of the Comet 40-150kVA. Installation of equipment must be handled by skilled technicians and electrician's familiar with the requirements of high energy electrical equipment. The installation must comply with the requirements of the National Electrical Code (NEC, ANSI/NFPA 70, latest issue) and with local codes and requirements as applicable. We strongly recommend contracting MGE Customer Support Services for startup. Do not allow unqualified personnel to handle or operate the equipment.

2.4.1Environmental

The Comet 40-150kVA UPS is intended for use in an environment where control of temperature and humidity is provided. The maximum operating and recommended environmental parameters are provided in the Specifications section of this document.

The Comet UPS generates heat and exhausts air through the top portion of its enclosure. Heat loss data is provided in Table 1-1.

Consult the installation drawings provided with your equipment.

2 — 2

Installation

86-160310-00 E00

Image 27
Contents Comet 40-150kVA Page Revision History CometComet 40-150kVA Important Safety InstructionsSpecial Precautions Certification Standards Three Phase UPSSafety of Persons Product SafetyThis page left blank intentionally Contents Operation MaintenanceTables MGE Warranty & Proprietary Rights for Three Phase ProductsWarranty and Product Registration Customer Care Center Three Phase ProductsUPS Serial Number Battery Serial Number This page left blank intentionally 86-160310-00 E00 Section Descriptions Comet 40-150kVA Symbol UsageSystem Description and Specifications ScopeGeneral Description Single Line Diagram for the Comet 40-80kVA Major Components Detail Behind Item Rear View of the Comet 40-80kVA FU1-FU21 Control Fuses TOP Conduit Landing for Cable Access to Pcas Specifications DC Ratings Battery voltage 25 C PhasesWires Power factorAltitude Environmental Specifications Temperature6 DB15 Connector Pinouts and Designations HumidityOptions and Accessories Chaptername This page left blank intentionally For assistance InstallationReceiving HandlingEnvironmental Prerequisite to InstallationStorage May adversely affect lifeElectrical Short circuit when the unit is working on Static SwitchProper trip settings MechanicalConnections Installation ProceduresAC Output BatteryChaptername This page left blank intentionally Operation Power FlowPower Flow, For Normal Operation Power Flow, For On Battery OperationPower Flow, For Bypass Operation Graphical User Interface, Controls and IndicatorsComet Front Panel GUI, Controls and Indicators Fault Reset Emergency Power OffFault LED Battery Status LEDStartup Procedures Inverter Manual StartupPreliminary Checks Return to AC Power Operating ProceduresOperation on Battery Power Battery DurationOutput Current Overload Curve Emergency Shutdown Using EPO/REPO Maintenance BypassForced Transfer Move the fan control switch SR2 to the OFF position Inverter Shutdown Shutdown ProceduresAlarms Powering DownMaintenance Battery SafetyPreventive Maintenance Level Description Replacement PartsApplicable within the United States, Canada and Mexico Warranty Extension Warranty+ User InformationProduct Information Return Policy for Repair of Three Phase Products RGA MGE Customer Care Center Three Phase ProductsTechnical Support and Product Services Scheduling Field Service Engineer SupportComet 40-150kVA Term used Definition / Meaning GlossaryFCC NEC This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Page Page Contact MGE