3.9Shutdown Procedures
3.9.1Inverter Shutdown
◗Press and hold the gray "Inverter OFF" pushbutton for 3 seconds.
◗The green “Load Protected” LED goes off.
◗The red “Load Not Protected” LED goes on.
◗The buzzer sounds.
◗The Inverter stops if the transfer conditions are correct.
◗The load is transferred and supplied via the "Static Switch".
3.9.2Powering Down
It is recommended not to power down the Comet for long periods because the battery should remained charged. However, to carry out a power down, proceed as follows:
◗Shut down the Inverter.
◗Put the battery circuit breaker in the "OFF" position.
◗Put the upstream main circuit breaker in the "OFF" position.
◗All the indicating LED's on the control panel go off.
3.10Alarms
Any state other than normal operation (green “Load Protected” LED on) is considered a fault by the diagnostics system.
Before undertaking any servicing or other action, note the status of the different LED's and the GUI messages displayed on the panel.
If an alarm is present and the load still functions, it is supplied via the "Static Switch", i.e. it is not protected. Table
beep beep
beep beep
beep beep
beep beep
status or action producing the indication
inverter
normal operation;
load supplied by Comet UPS (SR1 in normal position)
inverter shutdown following pressing of the "inverter off" button or a major fault;
load supplied via the "static switch"
operation on battery power; load supplied by Comet UPS
end of battery power or battery should be checked
minor fault;
(load continues to be supplied via inverter)
UPS shutdown;
load supplied via maintenance bypass
Legend of alarm indications table:
buzzer off,
light off,
beep |
|
beep | buzzer on, |
| |
| light on, |
| light flashing |
3 | Operation |