Installation and User Manual

3.5.4Overload

When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal mode of operation is automatic, following elimination of the overload.

The Inverter can handle a continuous overload for a given duration depending on the size of the output current overload (see Figure 3-5) or the output power overload (see Figure 3-6).

When an overload occurs:

The buzzer sounds.

The yellow "Fault" LED goes on.

The Inverter shuts down at the end of its corresponding overload time.

The load is supplied by AC input power via the "Static Switch".

The green "Load Protected" LED goes off.

The red "Load Not Protected" LED goes on.

The operating status of the UPS is provided by the GUI display. If the overload continues during operation via the "Static Switch", the supply of power to the load is interrupted after a specified time.

When the Comet shuts down because of a continuous overload, the "Fault Reset" key must be pressed prior to return to normal operation and after elimination of the overload.

Figure 3-5: Output Current Overload Curve.

time

10 mn

1mn 10 s

1 s

rated load current

0.15 s

1.05 1.1

1.3

1.5

1.7

1.9

3

I (A)

Figure 3-6: Output Power Overload Curve.

time

1mn 10 s

1 s

rated load

power

0.3 s

1.1

1.3

1.5

1.7

1.9

2

P (kw)

86-160310-00 E00

Operation

3 —7

Image 39
Contents Comet 40-150kVA Page Revision History CometComet 40-150kVA Important Safety InstructionsSpecial Precautions Certification Standards Three Phase UPSSafety of Persons Product SafetyThis page left blank intentionally Contents Operation MaintenanceTables MGE Warranty & Proprietary Rights for Three Phase ProductsWarranty and Product Registration Customer Care Center Three Phase ProductsUPS Serial Number Battery Serial Number This page left blank intentionally 86-160310-00 E00 Section Descriptions Comet 40-150kVA Symbol UsageSystem Description and Specifications ScopeGeneral Description Single Line Diagram for the Comet 40-80kVA Major Components Detail Behind Item Rear View of the Comet 40-80kVA FU1-FU21 Control Fuses TOP Conduit Landing for Cable Access to Pcas Specifications DC Ratings Battery voltage 25 C PhasesWires Power factorAltitude Environmental Specifications Temperature6 DB15 Connector Pinouts and Designations HumidityOptions and Accessories Chaptername This page left blank intentionally For assistance InstallationReceiving HandlingEnvironmental Prerequisite to InstallationStorage May adversely affect lifeElectrical Short circuit when the unit is working on Static SwitchProper trip settings MechanicalConnections Installation ProceduresAC Output BatteryChaptername This page left blank intentionally Operation Power FlowPower Flow, For Normal Operation Power Flow, For On Battery OperationPower Flow, For Bypass Operation Graphical User Interface, Controls and IndicatorsComet Front Panel GUI, Controls and Indicators Fault Reset Emergency Power OffFault LED Battery Status LEDStartup Procedures Inverter Manual StartupPreliminary Checks Return to AC Power Operating ProceduresOperation on Battery Power Battery DurationOutput Current Overload Curve Emergency Shutdown Using EPO/REPO Maintenance BypassForced Transfer Move the fan control switch SR2 to the OFF position Inverter Shutdown Shutdown ProceduresAlarms Powering DownMaintenance Battery SafetyPreventive Maintenance Level Description Replacement PartsApplicable within the United States, Canada and Mexico Warranty Extension Warranty+ User InformationProduct Information Return Policy for Repair of Three Phase Products RGA MGE Customer Care Center Three Phase ProductsTechnical Support and Product Services Scheduling Field Service Engineer SupportComet 40-150kVA Term used Definition / Meaning GlossaryFCC NEC This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Page Page Contact MGE