Installation and User Manual
3.5.4Overload
When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal mode of operation is automatic, following elimination of the overload.
The Inverter can handle a continuous overload for a given duration depending on the size of the output current overload (see Figure
When an overload occurs:
◗The buzzer sounds.
◗The yellow "Fault" LED goes on.
◗The Inverter shuts down at the end of its corresponding overload time.
◗The load is supplied by AC input power via the "Static Switch".
◗The green "Load Protected" LED goes off.
◗The red "Load Not Protected" LED goes on.
The operating status of the UPS is provided by the GUI display. If the overload continues during operation via the "Static Switch", the supply of power to the load is interrupted after a specified time.
When the Comet shuts down because of a continuous overload, the "Fault Reset" key must be pressed prior to return to normal operation and after elimination of the overload.
Figure 3-5: Output Current Overload Curve.
time
10 mn
1mn 10 s
1 s
rated load current
0.15 s
1.05 1.1 | 1.3 | 1.5 | 1.7 | 1.9 | 3 | I (A) |
Figure 3-6: Output Power Overload Curve.
time
1mn 10 s
1 s
rated load
power
0.3 s
1.1 | 1.3 | 1.5 | 1.7 | 1.9 | 2 | P (kw) |
Operation | 3 |