Installation and User Manual
2.4.2Mechanical
The Comet UPS can be mounted on a raised computer room floor, or
Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The Comet requires at least 36 inches top clearance for ventilation.
2.4.3Electrical
Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70, latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the installation drawings supplied with the equipment. The Comet 480/480V UPS is not a
CAUTION | The customer supplied upstream protective device shall open in one cycle | |
| when 10 times the output rated current is applied or in the event of an output | |
| short circuit when the unit is working on “Static Switch.” | |
| Refer to the upstream circuit breaker manufacturer’s characteristic curves for | |
| proper trip settings. | |
|
|
|
Table
INPUT VOLTAGE | 40kVA | 50kVA | 65kVA | 80kVA | 100kVA | 125kVA | 150kVA |
|
|
|
|
|
|
|
|
|
|
208 | 150A | 175A | 225A | 300A | 350A | 450A | 500A |
|
|
|
|
|
|
|
|
|
|
220 | 150A | 175A | 225A | 300A | 350A | 450A | 500A |
|
|
|
|
|
|
|
|
|
|
480 | 70A | 80A | 100A | 125A | 150A | 200A | 225A |
|
|
|
|
|
|
|
|
|
|
600 | 60A | 70A | 80A | 100A | 125A | 150A | 200A |
|
|
|
|
|
|
|
|
|
|
* Size determined using nominal input currents.
Installation | 2 — 3 |