MGE UPS Systems 40-150kVA user manual Mechanical, Electrical, Proper trip settings

Page 28

Installation and User Manual

2.4.2Mechanical

The Comet UPS can be mounted on a raised computer room floor, or flush-mounted on a concrete floor. All floors must be level. On a raised floor, conduits can be run below the floor, with cut-outs made in the floor tiles as shown on the installation drawings.

Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The Comet requires at least 36 inches top clearance for ventilation.

2.4.3Electrical

Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70, latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the installation drawings supplied with the equipment. The Comet 480/480V UPS is not a separately-derived source. The Comet 208/208V UPS is a separately derived source. The neutral must be grounded on a separately derived source (like the Comet 208/208V UPS).

CAUTION

The customer supplied upstream protective device shall open in one cycle

 

when 10 times the output rated current is applied or in the event of an output

 

short circuit when the unit is working on “Static Switch.”

 

Refer to the upstream circuit breaker manufacturer’s characteristic curves for

 

proper trip settings.

 

 

 

Table 2-1: Recommended upstream protective device sizing *.

INPUT VOLTAGE

40kVA

50kVA

65kVA

80kVA

100kVA

125kVA

150kVA

 

 

 

 

 

 

 

 

 

 

208

150A

175A

225A

300A

350A

450A

500A

 

 

 

 

 

 

 

 

 

 

220

150A

175A

225A

300A

350A

450A

500A

 

 

 

 

 

 

 

 

 

 

480

70A

80A

100A

125A

150A

200A

225A

 

 

 

 

 

 

 

 

 

 

600

60A

70A

80A

100A

125A

150A

200A

 

 

 

 

 

 

 

 

 

 

* Size determined using nominal input currents.

86-160310-00 E00

Installation

2 — 3

Image 28
Contents Comet 40-150kVA Page Comet Revision HistoryImportant Safety Instructions Comet 40-150kVACertification Standards Three Phase UPS Safety of PersonsProduct Safety Special PrecautionsThis page left blank intentionally Contents Maintenance OperationMGE Warranty & Proprietary Rights for Three Phase Products Warranty and Product RegistrationCustomer Care Center Three Phase Products TablesUPS Serial Number Battery Serial Number This page left blank intentionally 86-160310-00 E00 Comet 40-150kVA Symbol Usage Section DescriptionsScope System Description and SpecificationsGeneral Description Single Line Diagram for the Comet 40-80kVA Major Components Detail Behind Item Rear View of the Comet 40-80kVA FU1-FU21 Control Fuses TOP Conduit Landing for Cable Access to Pcas Specifications Phases WiresPower factor DC Ratings Battery voltage 25 CEnvironmental Specifications Temperature 6 DB15 Connector Pinouts and DesignationsHumidity AltitudeOptions and Accessories Chaptername This page left blank intentionally Installation ReceivingHandling For assistancePrerequisite to Installation StorageMay adversely affect life EnvironmentalShort circuit when the unit is working on Static Switch Proper trip settingsMechanical ElectricalInstallation Procedures ConnectionsBattery AC OutputChaptername This page left blank intentionally Power Flow Power Flow, For Normal OperationPower Flow, For On Battery Operation OperationGraphical User Interface, Controls and Indicators Power Flow, For Bypass OperationComet Front Panel GUI, Controls and Indicators Emergency Power Off Fault LEDBattery Status LED Fault ResetInverter Manual Startup Startup ProceduresPreliminary Checks Operating Procedures Operation on Battery PowerBattery Duration Return to AC PowerOutput Current Overload Curve Maintenance Bypass Emergency Shutdown Using EPO/REPOForced Transfer Move the fan control switch SR2 to the OFF position Shutdown Procedures AlarmsPowering Down Inverter ShutdownBattery Safety MaintenancePreventive Maintenance Replacement Parts Level DescriptionApplicable within the United States, Canada and Mexico User Information Warranty Extension Warranty+Product Information MGE Customer Care Center Three Phase Products Technical Support and Product ServicesScheduling Field Service Engineer Support Return Policy for Repair of Three Phase Products RGAComet 40-150kVA Glossary Term used Definition / MeaningFCC NEC This page left blank intentionally Reorder Form Scenic Avenue Costa Mesa, CA Page Page Contact MGE