American Power Conversion SYMSTRF-PD, SYMINIF-PD user manual System Setup

Page 47

Chapter 5 - System Setup

5-10

Image 47
Contents Syminif SYMINIF-PD Symstrf SYMSTRF-PD 990-7770A Revised 10/97 Radio Frequency InterferenceLife Support Policy Limited WarrantyTable of Contents Index Introduction Fig I-1MiniFrame and MasterFrame Fig I-2Functional Diagram of a SymmetraTMThank You SymmetraTM Overview Theory of OperationTransformer Power Processing SystemBattery Source Control/User InterfaceFig I-4On-Line Operating Mode Load-Disconnect ModeOn-Line Operating Mode Fig I-3Load-Disconnect Operating ModeFig I-6Bypass Operating Mode On-Battery Operating ModeBypass Operating Mode Fig I-5On-Battery Operating ModeImportant Information DefinitionsSafety Information Important Safety Instructions Symbols Used In This ManualTech Physical Representation 1A Fully Loaded MiniFrame grill covers removed Power Array Frame2An Empty MasterFrame grill covers removed Louvered Grill Covers Powerview User InterfacePower Module Battery ModuleInput Circuit Breaker Maintenance Bypass SwitchMain Intelligence Module MIM Redundant Intelligence Module RIMRear View of a Power Array Site Preparation BTU Output Space and Weight ConsiderationsTransporting Power Array to Installation Site Operating ConditionsSite Preparation Unpacking and Installing Frame Check For Damage Tools Required for SetupStorage of Battery and Power Modules Initial InspectionRemove the Frame from the Pallet Moving Battery & Power ModulesClean-UP Remove Packing MaterialsWiring Requirements & Procedures Repo Switch Wiring SymmetraTM WiringInput Wiring Output WiringVoltage Jumper Procedure Input WiringInput Wiring Specifications 5Input Hardwiring Configuration Input Wiring Procedure3Removal of Input Hardwiring Panels 4Input Wiring PathwayOutput Overcurrent Protection Output WiringOutput Wiring Configurations 8Output Wiring Configuration for 120V/240V Output Voltages Grounding Electrode Optional Output Wiring InstallationOutput Wiring Procedure Power Distribution Units OptionalCable Specifications Remote Emergency Power Off SwitchRepo Specifications Repo Switch InstallationVdc Repo Switch Connection Electrical Wiring TestElectrical Wiring Test/Checklist Contact Closure Repo Switch Connection4Input/Output Measured Voltage Multipliers 16Startup ScreenElectrical Requirements and Procedures Setting Up The Power Array 1Removing Cover Grills from Frame Setup of Power ArrayFrame Leveling Procedure Removing Cover Grills3Battery Alignment Grooves and Runners Installing the Battery ModulesProcedure for Battery Module Installation 2Location of Battery Module BaysProcedure for Power Module Installation Installing the Power Modules9Location of the MIM and RIM Installing the Main Intelligence Module MIMInstalling the Redundant Intelligence Module RIM Procedure for Main Intelligence Module MIM InstallationWall Mounting the PowerView Installing the PowerView InterfaceRemote Placement of the PowerView 13PowerView Wall Mounting Template SmartSlotTM Interface Accessories Installation Test/Checklist Installation Test20Miscellaneous Status Screen 19Power Status Screen1SymmetraTM Power Module/Frame Capacities 21Power The Load Sequence24Return to On-Line Sequence 25Power Down the Load Sequence23Initiate a Self-Test Sequence System Setup PowerView Display 1The PowerView Interface PowerView DisplayPhysical Features of the Powerview PowerView FunctionsNavigation Keys PowerView LEDs1Power Array Display LEDs Color DescriptionStatus Startup ScreenTop-Level Menu Screen ControlLogging SetupAccessories DiagnosticsConfiguring & Operating the SymmetraTM 1Startup Screen Powering the Power ArrayIntroduction Voltage Status Screen Powering the LoadsReview Status Conditions Load With Redundancy Status Screen Battery Status ScreenPower Status Screen Miscellaneous Status Screen Alarm Threshold Status ScreenPerform a Self Test Switching Audible Alarm Beeper Off Configure Shutdown ParametersConfigure Alarms Alarm Thresholds Selection ScreenEvent Log Screen Review Diagnostic InformationDiagnostics Menu Screen Review Logging MenuModule Replacement Returning Modules to APC Module ReplacementModule Failure Alarm Indicators Technical Support and Obtaining a Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementRemoving a Battery Module Installing the Replacement ModuleReplacement Module Verification Power Module ReplacementRemoving the Power Module Replacement MIM Verification Installing the Replacement Main Intelligence ModuleInstalling the Replacement Redundant Intelligence Module Replacement Redundant Intelligene Module VerificationPowerView Display Messages PowerView Message Meaning Corrective Action Start-Up Min Runtime restored PowerView Message Meaning Corrective Action General StatusThreshol PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassPowerView Message Meaning Corrective Action General Fault PowerView Display Messages Index Index SmartSlot accessories Toll free technical support