American Power Conversion SYMSTRF-PD, SYMINIF-PD user manual Removing the Main Intelligence Module

Page 64

Chapter 8 - Module Replacement

Main Intelligence Module

Redundant Intelligence Module

Replacement

Replacement

The following section provides the procedure for replacing the main intelligence module.

The following section provides the procedure for replacing the redundant intelligence module.

Removing the Main Intelligence Module

1.Remove the grill cover from the top level of the Power Array. Note: The intelligence module resides under the redundant intelli- gence module, in the upper right corner of the frame.

2.If a functioning RIM is not installed, the SymmetraTM must be placed in manual bypass mode, or the load equipment must be switched off. To place the SymmetraTM in manual bypass, switch the maintenance bypass switch to the “on” position.

Note: When the SymmetraTM is in bypass mode, the load equip- ment is unprotected from power failure.

3.If a functioning RIM is installed, it will provide limited control of the SymmetraTM until the replacement MIM is installed.

4.Use a flathead screwdriver to release the fliplatch.

5.Unscrew and release the retaining screws.

6.Slide the MIM out of the frame.

Installing the Replacement Main Intelligence Module

Refer to chapter 5 for the MIM installation procedure.

Note: If SymmetraTM was placed in manual bypass in step 2 above, return to normal operation by switching the maintenance bypass switch back to the “off” position.

Removing the Redundant Intelligence Module

1.Remove the grill cover from the top level of the Power Array. Note: The redundant intelligence module resides above the intelli- gence module, in the upper right corner of the frame.

2.A RIM can only be replaced if a functioning MIM is installed, or the load equipment is switched off.

3.Use a flathead screwdriver to release the fliplatch.

4.Unscrew and release the retaining screws.

5.Slide the RIM out of the frame.

Installing the Replacement Redundant Intelligence Module

Refer to chapter 5 for the RIM installation procedure.

Note: A RIM alone is not adequate to restart the SymmetraTM.

Replacement Redundant Intelligene Module Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-11 to insure that the replacement RIM is functioning properly. (Status: On & OK).

Replacement MIM Verification

From the startup screen, press any key to open the top level menu

screen. Follow the sequence in figure 8-10 to insure that the Fig 8-11Redundant Intelligence Module Verification replacement MIM is functioning properly. (Status: On & OK).

Fig 8-10Intelligence Module Verification

8-4

Image 64
Contents Syminif SYMINIF-PD Symstrf SYMSTRF-PD Radio Frequency Interference 990-7770A Revised 10/97Limited Warranty Life Support PolicyTable of Contents Index Introduction Fig I-2Functional Diagram of a SymmetraTM Thank You SymmetraTM OverviewTheory of Operation Fig I-1MiniFrame and MasterFramePower Processing System Battery SourceControl/User Interface TransformerLoad-Disconnect Mode On-Line Operating ModeFig I-3Load-Disconnect Operating Mode Fig I-4On-Line Operating ModeOn-Battery Operating Mode Bypass Operating ModeFig I-5On-Battery Operating Mode Fig I-6Bypass Operating ModeDefinitions Important InformationSafety Information Symbols Used In This Manual Important Safety InstructionsTech Physical Representation 2An Empty MasterFrame grill covers removed Power Array Frame1A Fully Loaded MiniFrame grill covers removed Powerview User Interface Power ModuleBattery Module Louvered Grill CoversMaintenance Bypass Switch Main Intelligence Module MIMRedundant Intelligence Module RIM Input Circuit BreakerRear View of a Power Array Site Preparation Space and Weight Considerations Transporting Power Array to Installation SiteOperating Conditions BTU OutputSite Preparation Unpacking and Installing Frame Tools Required for Setup Storage of Battery and Power ModulesInitial Inspection Check For DamageMoving Battery & Power Modules Clean-UPRemove Packing Materials Remove the Frame from the PalletWiring Requirements & Procedures SymmetraTM Wiring Input WiringOutput Wiring Repo Switch WiringInput Wiring Specifications Input WiringVoltage Jumper Procedure Input Wiring Procedure 3Removal of Input Hardwiring Panels4Input Wiring Pathway 5Input Hardwiring ConfigurationOutput Wiring Configurations Output WiringOutput Overcurrent Protection 8Output Wiring Configuration for 120V/240V Output Voltages Output Wiring Installation Output Wiring ProcedurePower Distribution Units Optional Grounding Electrode OptionalRemote Emergency Power Off Switch Repo SpecificationsRepo Switch Installation Cable SpecificationsElectrical Wiring Test Electrical Wiring Test/ChecklistContact Closure Repo Switch Connection Vdc Repo Switch Connection16Startup Screen 4Input/Output Measured Voltage MultipliersElectrical Requirements and Procedures Setting Up The Power Array Setup of Power Array Frame Leveling ProcedureRemoving Cover Grills 1Removing Cover Grills from FrameInstalling the Battery Modules Procedure for Battery Module Installation2Location of Battery Module Bays 3Battery Alignment Grooves and RunnersInstalling the Power Modules Procedure for Power Module InstallationInstalling the Main Intelligence Module MIM Installing the Redundant Intelligence Module RIMProcedure for Main Intelligence Module MIM Installation 9Location of the MIM and RIMRemote Placement of the PowerView Installing the PowerView InterfaceWall Mounting the PowerView SmartSlotTM Interface Accessories 13PowerView Wall Mounting TemplateInstallation Test Installation Test/Checklist19Power Status Screen 1SymmetraTM Power Module/Frame Capacities21Power The Load Sequence 20Miscellaneous Status Screen23Initiate a Self-Test Sequence 25Power Down the Load Sequence24Return to On-Line Sequence System Setup PowerView Display PowerView Display Physical Features of the PowerviewPowerView Functions 1The PowerView InterfacePowerView LEDs 1Power Array Display LEDsColor Description Navigation KeysStartup Screen Top-Level Menu ScreenControl StatusSetup AccessoriesDiagnostics LoggingConfiguring & Operating the SymmetraTM Introduction Powering the Power Array1Startup Screen Review Status Conditions Powering the LoadsVoltage Status Screen Power Status Screen Battery Status ScreenLoad With Redundancy Status Screen Perform a Self Test Alarm Threshold Status ScreenMiscellaneous Status Screen Configure Shutdown Parameters Configure AlarmsAlarm Thresholds Selection Screen Switching Audible Alarm Beeper OffReview Diagnostic Information Diagnostics Menu ScreenReview Logging Menu Event Log ScreenModule Replacement Module Replacement Module Failure Alarm IndicatorsTechnical Support and Obtaining a Replacement Module Returning Modules to APCBattery Module Replacement Removing a Battery ModuleInstalling the Replacement Module Replacement Battery Module VerificationRemoving the Power Module Power Module ReplacementReplacement Module Verification Installing the Replacement Main Intelligence Module Installing the Replacement Redundant Intelligence ModuleReplacement Redundant Intelligene Module Verification Replacement MIM VerificationPowerView Display Messages PowerView Message Meaning Corrective Action Start-Up PowerView Message Meaning Corrective Action General Status Min Runtime restoredPowerView Meaning Corrective Action Message Module AlarmFailure ThresholPowerView Meaning Corrective Action Message Bypass FaultPowerView Message Meaning Corrective Action General Fault PowerView Display Messages Index Index SmartSlot accessories Toll free technical support