American Power Conversion SYMINIF, SYMSTRF-PD Power Module Replacement, Removing the Power Module

Page 63

 

Chapter 8 - Module Replacement

Power Module Replacement

 

The following section provides the procedure for replacing a

 

power module.

 

Removing the Power Module

 

1. Remove the grill cover from in front of the module to be

 

replaced. Note that the module bays are labelled to corre-

 

spond with the PowerView display.

 

2. If replacing a non-redundant power module, or if the power

 

module to be replaced is the only power module present, the

 

SymmetraTM must be placed in manual bypass mode, or the

 

load equipment must be switched off. To place the SymmetraTM

 

in manual bypass, switch the maintenance bypass switch to

 

the “on” position.

 

Note: When the SymmetraTM is in bypass mode, the load equip-

 

ment is unprotected from power failure.

Drop Lock

3. Use a flathead screwdriver to release the fliplatch from the

Seating Tabs

power module. See figure 8-7.

 

Fig 8-7Release the Flip Latch

4.Note the two drop lock seating tabs at the front of the power module. See Figure 8-8. These are designed to hold the module firmly in the Power Array frame. When removing a failed power module, lift the front of the module slightly to release the drop lock seating tabs, and then pull the module from the bay.

5.Remove the power module from the frame. If the module has failed and needs to be disposed of, return it to the appro- priate service provider, or directly to APC.

Fig 8-8Drop Lock Seating Tabs

Installing the Replacement Module

Refer to chapter 5 for the power module installation proce- dure.

Note: If SymmetraTM was placed in manual bypass in step 2 above, return to normal operation by switching the mainte- nance bypass switch back to the “off” position.

Replacement Module Verification

From the startup screen, press any key to open the top level menu screen. Follow the sequence in figure 8-9 to insure that the new module is functioning properly. Note that the up/ down cursor appears, and the information for each power module is reviewed by pressing the up or down navigation key. Make sure all power modules display a status of “On & OK.”

Fig 8-9Power Module Verification

8-3

Image 63
Contents Syminif SYMINIF-PD Symstrf SYMSTRF-PD 990-7770A Revised 10/97 Radio Frequency InterferenceLife Support Policy Limited WarrantyTable of Contents Index Introduction Fig I-1MiniFrame and MasterFrame Fig I-2Functional Diagram of a SymmetraTMThank You SymmetraTM Overview Theory of OperationTransformer Power Processing SystemBattery Source Control/User InterfaceFig I-4On-Line Operating Mode Load-Disconnect ModeOn-Line Operating Mode Fig I-3Load-Disconnect Operating ModeFig I-6Bypass Operating Mode On-Battery Operating ModeBypass Operating Mode Fig I-5On-Battery Operating ModeImportant Information DefinitionsSafety Information Important Safety Instructions Symbols Used In This ManualTech Physical Representation Power Array Frame 2An Empty MasterFrame grill covers removed1A Fully Loaded MiniFrame grill covers removed Louvered Grill Covers Powerview User InterfacePower Module Battery ModuleInput Circuit Breaker Maintenance Bypass SwitchMain Intelligence Module MIM Redundant Intelligence Module RIMRear View of a Power Array Site Preparation BTU Output Space and Weight ConsiderationsTransporting Power Array to Installation Site Operating ConditionsSite Preparation Unpacking and Installing Frame Check For Damage Tools Required for SetupStorage of Battery and Power Modules Initial InspectionRemove the Frame from the Pallet Moving Battery & Power ModulesClean-UP Remove Packing MaterialsWiring Requirements & Procedures Repo Switch Wiring SymmetraTM WiringInput Wiring Output WiringInput Wiring Input Wiring SpecificationsVoltage Jumper Procedure 5Input Hardwiring Configuration Input Wiring Procedure3Removal of Input Hardwiring Panels 4Input Wiring PathwayOutput Wiring Output Wiring ConfigurationsOutput Overcurrent Protection 8Output Wiring Configuration for 120V/240V Output Voltages Grounding Electrode Optional Output Wiring InstallationOutput Wiring Procedure Power Distribution Units OptionalCable Specifications Remote Emergency Power Off SwitchRepo Specifications Repo Switch InstallationVdc Repo Switch Connection Electrical Wiring TestElectrical Wiring Test/Checklist Contact Closure Repo Switch Connection4Input/Output Measured Voltage Multipliers 16Startup ScreenElectrical Requirements and Procedures Setting Up The Power Array 1Removing Cover Grills from Frame Setup of Power ArrayFrame Leveling Procedure Removing Cover Grills3Battery Alignment Grooves and Runners Installing the Battery ModulesProcedure for Battery Module Installation 2Location of Battery Module BaysProcedure for Power Module Installation Installing the Power Modules9Location of the MIM and RIM Installing the Main Intelligence Module MIMInstalling the Redundant Intelligence Module RIM Procedure for Main Intelligence Module MIM InstallationInstalling the PowerView Interface Remote Placement of the PowerViewWall Mounting the PowerView 13PowerView Wall Mounting Template SmartSlotTM Interface AccessoriesInstallation Test/Checklist Installation Test20Miscellaneous Status Screen 19Power Status Screen1SymmetraTM Power Module/Frame Capacities 21Power The Load Sequence25Power Down the Load Sequence 23Initiate a Self-Test Sequence24Return to On-Line Sequence System Setup PowerView Display 1The PowerView Interface PowerView DisplayPhysical Features of the Powerview PowerView FunctionsNavigation Keys PowerView LEDs1Power Array Display LEDs Color DescriptionStatus Startup ScreenTop-Level Menu Screen ControlLogging SetupAccessories DiagnosticsConfiguring & Operating the SymmetraTM Powering the Power Array Introduction1Startup Screen Powering the Loads Review Status ConditionsVoltage Status Screen Battery Status Screen Power Status ScreenLoad With Redundancy Status Screen Alarm Threshold Status Screen Perform a Self TestMiscellaneous Status Screen Switching Audible Alarm Beeper Off Configure Shutdown ParametersConfigure Alarms Alarm Thresholds Selection ScreenEvent Log Screen Review Diagnostic InformationDiagnostics Menu Screen Review Logging MenuModule Replacement Returning Modules to APC Module ReplacementModule Failure Alarm Indicators Technical Support and Obtaining a Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementRemoving a Battery Module Installing the Replacement ModulePower Module Replacement Removing the Power ModuleReplacement Module Verification Replacement MIM Verification Installing the Replacement Main Intelligence ModuleInstalling the Replacement Redundant Intelligence Module Replacement Redundant Intelligene Module VerificationPowerView Display Messages PowerView Message Meaning Corrective Action Start-Up Min Runtime restored PowerView Message Meaning Corrective Action General StatusThreshol PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassPowerView Message Meaning Corrective Action General Fault PowerView Display Messages Index Index SmartSlot accessories Toll free technical support