Chapter 9 - PowerView Display Messages
PowerView
Message
Meaning
Corrective Action
General
Fault
Fault, Internal Temp | The temperature of one or more | Replace the overheated modules. | |
Refer to chapter 8 for module | |||
exceeded normal limits | battery modules is too hot. | ||
replacement procedures. | |||
|
| ||
|
|
| |
|
| Option #1: If this occurs in | |
|
| conjunction with an overload | |
| The input circuit breaker on the | condition, decrease the load and | |
| reset the breaker. | ||
Input circuit breaker | SymmetraTM has tripped. | ||
Option #1: If no overload condition | |||
tripped open | Input voltage is disconnected to | ||
exists, reset breaker. If it trips again, | |||
| the SymmetraTM. | ||
| call your contract service provider, | ||
|
| ||
|
| or APC technical support at: | |
|
| ||
|
|
| |
| A cooling fan in the SymmetraTM | Call your contract service provider, | |
System level fan failed | or APC technical support at: | ||
frame has failed. | |||
| |||
|
| ||
|
|
| |
| The main intelligence module has | Replace the intelligence module. | |
The Redundant Intelligence | failed, and the RIM is functioning | Refer to chapter 8 for module | |
Module is in control | as the primary intelligence | replacement procedures. | |
| module. | ||
|
| ||
|
|
| |
IIC | The communications between | Call your contract service provider, | |
the MIM and at least one other | or APC technical support at: | ||
communications failed. | |||
module has failed. | |||
| |||
|
|
|