Chapter 9 - PowerView Display Messages

PowerView

Message

Meaning

Corrective Action

General

Status

# of batteries increased.

At least one battery module has

No corrective action necessary.

been added to the system.

 

 

 

 

 

# of batteries decreased.

At least one battery module has

No corrective action necessary.

been removed from the system.

 

 

 

 

 

# of Pwr Modules

At least one power module has

No corrective action necessary.

increased.

been added to the system.

 

 

 

 

# of Pwr Modules

At least one power module has

No corrective action necessary.

decreased.

been removed from the system.

 

 

 

 

Intelligence Module

A MIM has been installed into the

No corrective action necessary.

inserted.

SymmetraTM .

 

 

 

 

Intelligence Module

A MIM has been removed from the

No corrective action necessary.

removed

SymmetraTM .

 

 

 

 

Redundant Intelligence

A RIM has been installed into the

No corrective action necessary.

Module inserted.

SymmetraTM .

 

 

 

 

Redundant Intelligemce

A RIM has been removed from the

No corrective action necessary.

Module removed.

SymmetraTM .

 

 

 

 

# of External Battery

At least one external battery cabinet

No corrective action necessary.

Cabinets increased.

has been connected to the frame.

 

 

 

 

# of External Battery

At least one external battery

No corrective action necessary.

cabinets has been disconnected

Cabinets decreased.

from the SymmetraTM.

 

 

 

 

 

 

 

A loss of power module redundancy

 

 

occurred, and has been restored.

 

Redundancy Restored

Either additional modules have been

No corrective action necessary.

 

installed, or the load has been

 

 

reduced.

 

 

 

 

 

The load had exceeded the load

 

Load is No Longer above

alarm threshold. The situation has

 

been corrected either because the

No corrective action necessary.

Alarm Threshold

load decreased, or the threshold

 

 

 

 

was increased.

 

 

 

 

 

The system runtime had dropped

 

 

below the configured minimum, and

 

 

has been restored. Either additional

 

Min Runtime restored.

battery modules were installed, the

No corrective action necessary.

 

existing battery modules recharged,

 

 

the load was reduced, or the

 

 

threshold was raised.

 

 

 

 

9-2

Image 67
Contents Syminif SYMINIF-PD Symstrf SYMSTRF-PD 990-7770A Revised 10/97 Radio Frequency InterferenceLife Support Policy Limited WarrantyTable of Contents Index Introduction Fig I-1MiniFrame and MasterFrame Fig I-2Functional Diagram of a SymmetraTMThank You SymmetraTM Overview Theory of OperationTransformer Power Processing SystemBattery Source Control/User InterfaceFig I-4On-Line Operating Mode Load-Disconnect ModeOn-Line Operating Mode Fig I-3Load-Disconnect Operating ModeFig I-6Bypass Operating Mode On-Battery Operating ModeBypass Operating Mode Fig I-5On-Battery Operating ModeImportant Information DefinitionsSafety Information Important Safety Instructions Symbols Used In This ManualTech Physical Representation 2An Empty MasterFrame grill covers removed Power Array Frame1A Fully Loaded MiniFrame grill covers removed Louvered Grill Covers Powerview User InterfacePower Module Battery ModuleInput Circuit Breaker Maintenance Bypass SwitchMain Intelligence Module MIM Redundant Intelligence Module RIMRear View of a Power Array Site Preparation BTU Output Space and Weight ConsiderationsTransporting Power Array to Installation Site Operating ConditionsSite Preparation Unpacking and Installing Frame Check For Damage Tools Required for SetupStorage of Battery and Power Modules Initial InspectionRemove the Frame from the Pallet Moving Battery & Power ModulesClean-UP Remove Packing MaterialsWiring Requirements & Procedures Repo Switch Wiring SymmetraTM WiringInput Wiring Output WiringInput Wiring Specifications Input WiringVoltage Jumper Procedure 5Input Hardwiring Configuration Input Wiring Procedure3Removal of Input Hardwiring Panels 4Input Wiring PathwayOutput Wiring Configurations Output WiringOutput Overcurrent Protection 8Output Wiring Configuration for 120V/240V Output Voltages Grounding Electrode Optional Output Wiring InstallationOutput Wiring Procedure Power Distribution Units OptionalCable Specifications Remote Emergency Power Off SwitchRepo Specifications Repo Switch InstallationVdc Repo Switch Connection Electrical Wiring TestElectrical Wiring Test/Checklist Contact Closure Repo Switch Connection4Input/Output Measured Voltage Multipliers 16Startup ScreenElectrical Requirements and Procedures Setting Up The Power Array 1Removing Cover Grills from Frame Setup of Power ArrayFrame Leveling Procedure Removing Cover Grills3Battery Alignment Grooves and Runners Installing the Battery ModulesProcedure for Battery Module Installation 2Location of Battery Module BaysProcedure for Power Module Installation Installing the Power Modules9Location of the MIM and RIM Installing the Main Intelligence Module MIMInstalling the Redundant Intelligence Module RIM Procedure for Main Intelligence Module MIM InstallationRemote Placement of the PowerView Installing the PowerView InterfaceWall Mounting the PowerView 13PowerView Wall Mounting Template SmartSlotTM Interface AccessoriesInstallation Test/Checklist Installation Test20Miscellaneous Status Screen 19Power Status Screen1SymmetraTM Power Module/Frame Capacities 21Power The Load Sequence23Initiate a Self-Test Sequence 25Power Down the Load Sequence24Return to On-Line Sequence System Setup PowerView Display 1The PowerView Interface PowerView DisplayPhysical Features of the Powerview PowerView FunctionsNavigation Keys PowerView LEDs1Power Array Display LEDs Color DescriptionStatus Startup ScreenTop-Level Menu Screen ControlLogging SetupAccessories DiagnosticsConfiguring & Operating the SymmetraTM Introduction Powering the Power Array1Startup Screen Review Status Conditions Powering the LoadsVoltage Status Screen Power Status Screen Battery Status ScreenLoad With Redundancy Status Screen Perform a Self Test Alarm Threshold Status ScreenMiscellaneous Status Screen Switching Audible Alarm Beeper Off Configure Shutdown ParametersConfigure Alarms Alarm Thresholds Selection ScreenEvent Log Screen Review Diagnostic InformationDiagnostics Menu Screen Review Logging MenuModule Replacement Returning Modules to APC Module ReplacementModule Failure Alarm Indicators Technical Support and Obtaining a Replacement ModuleReplacement Battery Module Verification Battery Module ReplacementRemoving a Battery Module Installing the Replacement ModuleRemoving the Power Module Power Module ReplacementReplacement Module Verification Replacement MIM Verification Installing the Replacement Main Intelligence Module Installing the Replacement Redundant Intelligence Module Replacement Redundant Intelligene Module VerificationPowerView Display Messages PowerView Message Meaning Corrective Action Start-Up Min Runtime restored PowerView Message Meaning Corrective Action General StatusThreshol PowerView Meaning Corrective Action Message ModuleAlarm FailureFault PowerView Meaning Corrective Action Message BypassPowerView Message Meaning Corrective Action General Fault PowerView Display Messages Index Index SmartSlot accessories Toll free technical support