American Power Conversion SYMINIF-PD, SYMSTRF-PD user manual Installing the PowerView Interface

Page 42

Chapter 5 - System Setup

Installing the PowerView Interface

An 18” RJ45 cable (supplied) is provided in bay“L1.” It is used to connect the PowerView to the Power Array. Use the follow- ing procedure to install the PowerView interface to the front of the frame.

1. Remove the cover grill from the top level of the frame.

2. Feed the end of the RJ45 cable through the center slot of the top cover grill, and replace the cover grill onto the frame. See figure 5-10.

Fig 5-10PowerView Cable Through Cover Grill

3.Connect the RJ45 plug into the receptacle on the back of the PowerView as shown in figure 5-11.

Fig 5-11Attaching the Cable to the PowerView

5.Position the PowerView over the mounting post on the front of the frame, and push straight down. The PowerView snaps into place. See figure 5-12.

6.Tuck the excess cable into the grill cover.

Fig 5-12Install PowerView Onto Frame

Remote Placement of the PowerView

The PowerView can be mounted at a remote location, up to 20’ from the frame. Follow the steps below to install PowerView in a remote location.

1.A 20’ RJ45 cable is included with the SymmetraTM Power Array.

2.Connect one end of the RJ45 cable to the rear of the Power Array frame. See figure 1-8 in chapter 1.

3.Connect the other end of the cable to the receptacle at the rear of the PowerView interface.

4.The short RJ45 cable at the top of power module bay “L1” can be safely tucked onto the top of the power module. Re- place the grill cover.

The PowerView will sit upright on a flat surface, by folding out the wire bail on the back. It can also be mounted to a wall.

Wall Mounting the PowerView

1.Note the four mounting slots molded into the back of the PowerView body.

2.Use the template in figure 5-13 to position four large screws on a clean dry wall surface.

3.Leave the head of each screw 5/16" out from the surface of the wall. Screws must be able to support 15lb.

4.Mount the PowerView display onto the wall by positioning it over the screws, and sliding it down until it is securely in place.

5-5

Image 42
Contents Syminif SYMINIF-PD Symstrf SYMSTRF-PD Radio Frequency Interference 990-7770A Revised 10/97Limited Warranty Life Support PolicyTable of Contents Index Introduction Theory of Operation Fig I-2Functional Diagram of a SymmetraTMThank You SymmetraTM Overview Fig I-1MiniFrame and MasterFrameControl/User Interface Power Processing SystemBattery Source TransformerFig I-3Load-Disconnect Operating Mode Load-Disconnect ModeOn-Line Operating Mode Fig I-4On-Line Operating ModeFig I-5On-Battery Operating Mode On-Battery Operating ModeBypass Operating Mode Fig I-6Bypass Operating ModeDefinitions Important InformationSafety Information Symbols Used In This Manual Important Safety InstructionsTech Physical Representation Power Array Frame 2An Empty MasterFrame grill covers removed1A Fully Loaded MiniFrame grill covers removed Battery Module Powerview User InterfacePower Module Louvered Grill CoversRedundant Intelligence Module RIM Maintenance Bypass SwitchMain Intelligence Module MIM Input Circuit BreakerRear View of a Power Array Site Preparation Operating Conditions Space and Weight ConsiderationsTransporting Power Array to Installation Site BTU OutputSite Preparation Unpacking and Installing Frame Initial Inspection Tools Required for SetupStorage of Battery and Power Modules Check For DamageRemove Packing Materials Moving Battery & Power ModulesClean-UP Remove the Frame from the PalletWiring Requirements & Procedures Output Wiring SymmetraTM WiringInput Wiring Repo Switch WiringInput Wiring Input Wiring SpecificationsVoltage Jumper Procedure 4Input Wiring Pathway Input Wiring Procedure3Removal of Input Hardwiring Panels 5Input Hardwiring ConfigurationOutput Wiring Output Wiring ConfigurationsOutput Overcurrent Protection 8Output Wiring Configuration for 120V/240V Output Voltages Power Distribution Units Optional Output Wiring InstallationOutput Wiring Procedure Grounding Electrode OptionalRepo Switch Installation Remote Emergency Power Off SwitchRepo Specifications Cable SpecificationsContact Closure Repo Switch Connection Electrical Wiring TestElectrical Wiring Test/Checklist Vdc Repo Switch Connection16Startup Screen 4Input/Output Measured Voltage MultipliersElectrical Requirements and Procedures Setting Up The Power Array Removing Cover Grills Setup of Power ArrayFrame Leveling Procedure 1Removing Cover Grills from Frame2Location of Battery Module Bays Installing the Battery ModulesProcedure for Battery Module Installation 3Battery Alignment Grooves and RunnersInstalling the Power Modules Procedure for Power Module InstallationProcedure for Main Intelligence Module MIM Installation Installing the Main Intelligence Module MIMInstalling the Redundant Intelligence Module RIM 9Location of the MIM and RIMInstalling the PowerView Interface Remote Placement of the PowerViewWall Mounting the PowerView SmartSlotTM Interface Accessories 13PowerView Wall Mounting TemplateInstallation Test Installation Test/Checklist21Power The Load Sequence 19Power Status Screen1SymmetraTM Power Module/Frame Capacities 20Miscellaneous Status Screen25Power Down the Load Sequence 23Initiate a Self-Test Sequence24Return to On-Line Sequence System Setup PowerView Display PowerView Functions PowerView DisplayPhysical Features of the Powerview 1The PowerView InterfaceColor Description PowerView LEDs1Power Array Display LEDs Navigation KeysControl Startup ScreenTop-Level Menu Screen StatusDiagnostics SetupAccessories LoggingConfiguring & Operating the SymmetraTM Powering the Power Array Introduction1Startup Screen Powering the Loads Review Status ConditionsVoltage Status Screen Battery Status Screen Power Status ScreenLoad With Redundancy Status Screen Alarm Threshold Status Screen Perform a Self TestMiscellaneous Status Screen Alarm Thresholds Selection Screen Configure Shutdown ParametersConfigure Alarms Switching Audible Alarm Beeper OffReview Logging Menu Review Diagnostic InformationDiagnostics Menu Screen Event Log ScreenModule Replacement Technical Support and Obtaining a Replacement Module Module ReplacementModule Failure Alarm Indicators Returning Modules to APCInstalling the Replacement Module Battery Module ReplacementRemoving a Battery Module Replacement Battery Module VerificationPower Module Replacement Removing the Power ModuleReplacement Module Verification Replacement Redundant Intelligene Module Verification Installing the Replacement Main Intelligence ModuleInstalling the Replacement Redundant Intelligence Module Replacement MIM VerificationPowerView Display Messages PowerView Message Meaning Corrective Action Start-Up PowerView Message Meaning Corrective Action General Status Min Runtime restoredFailure PowerView Meaning Corrective Action Message ModuleAlarm ThresholPowerView Meaning Corrective Action Message Bypass FaultPowerView Message Meaning Corrective Action General Fault PowerView Display Messages Index Index SmartSlot accessories Toll free technical support