Chapter 9 - PowerView Display Messages
| PowerView | Meaning | Corrective Action | |
| Message | |||
|
|
| ||
|
|
|
| |
Module | Bad Battery Module | A battery module has failed, and | Refer to chapter 8 for module | |
Failure | requires replacement. | replacement procedure. | ||
| ||||
|
|
|
| |
| Bad Power Module | A power module has failed, and | Refer to chapter 8 for module | |
| requires replacement. | replacement procedure. | ||
|
| |||
|
|
|
| |
| Intelligence Module is | The main intelligence module has | Refer to chapter 8 for module | |
| installed and failed | failed, and requires replacement. | replacement procedure. | |
|
|
|
| |
| Redundant Intelligence | The redundant intelligence | Refer to chapter 8 for module | |
| Module is installed and | module has failed, and requires | ||
| replacement procedure. | |||
| failed | replacement. | ||
|
| |||
|
|
|
| |
Threshol- | Load is above kVA alarm | The load has exceeded the user | Option #1: Reduce the load. | |
d Alarm | threshold | specified load alarm threshold. | Option #2: Use the PowerView to | |
|
|
| raise the alarm threshold. | |
|
|
| Option #1: If possible, install | |
|
| SymmetraTM no longer detects | additional power modules. | |
|
| Option #2: Decrease the load. | ||
|
| redundant power modules. | ||
| Redundancy has been lost. | Option #3: Disable the redundancy | ||
| Either power module(s) have | |||
|
| alarm by setting redundancy to zero. | ||
|
| failed, or the load has increased. | ||
|
| |||
|
|
| select zero.) | |
|
|
|
| |
|
| Actual power module | Option #1: If possible, install | |
|
| additional power modules. | ||
|
| redundancy has fallen below the | ||
|
| Option #2: Decrease the load. | ||
| Redundancy is below | user specified redundancy alarm | ||
| Option #3: Use the PowerView to | |||
| alarm threshold. | threshold. Either power | ||
| decrease the redundancy alarm | |||
|
| module(s) have failed, or the | ||
|
| threshold. | ||
|
| load has increased. | ||
|
| |||
|
|
| ||
|
|
|
| |
|
|
| Option #1: Allow the battery | |
|
| The predicted runtime is lower | modules to recharge. | |
|
| Option #2: If possible, increase the | ||
|
| than the user specified minimum | ||
|
| number of battery modules. | ||
| Runtime is below alarm | runtime alarm threshold. Either | ||
| Option #3: Decrease the load. | |||
| threshold. | the battery capacity has | ||
| Option #4: Use the PowerView to | |||
|
| decreased, or the load has | ||
|
| decrease the minimum runtime alarm | ||
|
| increased. | ||
|
| threshold. | ||
|
|
| ||
|
|
| ||
|
|
|
| |
Bypass |
| The frequency and/or voltage is | Option #1: Decrease the sensitivity | |
|
| out of acceptable range for | to input frequency. | |
| Bypass is not in range | bypass. This message occurs | ||
| (either freq or voltage) | when SymmetraTM is on line, and | Option #2: Corrrect input voltage | |
|
| indicates that the bypass mode | to provide acceptable voltage and/or | |
|
| may not be available if required. | frequency. | |
|
|
|
| |
| Bypass contactor stuck in | SymmetraTM is stuck in the | Call your contract service provider, | |
| bypass position, and cannot go | or APC Technical Support at: | ||
| bypass position. | |||
| online. | |||
|
| |||
|
|
|
| |
|
|
|
|