APC 6739380EN/JC user manual Hidden control panel

Page 18

Control panel (cont.)

"Inverter off" button

!

!

+ –

I

O

7

This gray button 7 turns the inverter off.

press the "inverter off" button 7 for

3 seconds;

if the transfer to Mains 2 conditions are correct:

the load is transferred without interrupting to Mains 2,

the inverter shuts down,

the green "load protected" light 5 goes off and the red "load not protected" light 2 goes on.

if the transfer to Mains 2 conditions are not correct, the button produces no effect. A special function on the hidden panel may be used to force the transfer.

Caution:

If the transfer is forced, the load will be subjected to a 0.8 second interruption in the supply of power.

Note:

for Modular UPSs or parallel UPSs with SSC, the shutdown of an inverter may or may not result in the transfer of the load to Mains 2, depending on redundancy conditions;

if the transfer to Mains 2 conditions are not correct or if the system does not have a Mains 2, the shutdown of a single inverter will result in the shutdown of the entire system if there is no redundancy.

Hidden control panel

The hidden panel, located behind the hinged cover, offers the following indications and control functions:

environment faults;

general faults in system modules;

special control buttons

(see figure 28).

This panel is identical for all types of cubicles, however, the controls or indications 8 that do not concern a given cubicle are not activated.

Clear fault log

This button 10 clears the alarms stored in memory. The memory may not be cleared until the cause of the alarms has ceased.

Hidden control panel (Inverter and Static Switch Cubicles)

 

 

 

 

 

 

8

 

 

 

 

 

A B C D E F G H I J K L M N

 

fault

 

1

2

 

3

4

5

9

10

11

12

13

14

15

16

17

Fig. 28

Buzzer reset

This button 11 stops the buzzer. A new fault starts the buzzer again.

Battery charge cycle

This button 12 starts a battery charge cycle (vented lead-acid batteries only). The cycle duration may be programmed (default value is 24 hours). Then the RC automatically shifts to "floating" mode.

Return to float charge

This button 13 can be used during a charge cycle to force the RC to return to "floating" mode.

Security button

This button 14 avoids inadvertent operation of the remaining three control buttons:

Mains 2 synchronization or desynchronization;

forced transfer to inverter with load interruption;

Page 18 - 6739380EN/JC

forced inverter shutdown with load interruption;

When pressing one of the above three buttons, the security button must also be pressed at the same time.

Mains 2 synchronization or desynchronization

This button 15 desynchronizes or resynchronizes the inverter output frequency with that of Mains 2.

Note:

for parallel-connected modular UPSs, this function must be carried out on all the UPSs.

Forced transfer to inverter with load interruption

This button 16 transfers the load to the inverter. If the transfer conditions (Mains 2 characteristics outside tolerances) are not correct, the transfer will result in a 0.8 second interruption in the supply of power to the load.

Note:

for parallel-connected modular UPSs, forced transfer of the load will not take place if the number of operating UPSs required by the load is greater than one;

for parallel UPSs with centralised SSC, this function is available only on the SSC.

Forced inverter shutdown with load interruption

This button 17 :

transfers the load to Mains 2;

shuts down the inverter.

It may be used if the transfer conditions (Mains 2 characteristics outside tolerances) are not correct, in which case the "inverter off" button 7 on the visible control panel produces no effect;

is disabled on the SSC.

Image 18
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System description IntroductionSystem performance System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Frequency converters with redundancy Output voltage quality and continuityFrequency converters without redundancy Overload curve250 to 400kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 450 to 500kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Visible control panel Static Switch CubicleControl panel Mgetm GalaxyTM 6000 control panelLoad not protected light Buzzer Operating problem lightBattery operation light Load protected lightHidden control panel Light H inverter fault Light F battery temperature outside tolerancesLight G battery charging Light I battery dischargedSingle-unit or modular UPS Start-upSystem start-up Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSFrequency converters Parallel UPS systems with a Static Switch CubicleStart-up of a unit Start-up of a rectifier/chargerSingle-unit or modular UPS system Frequency converter without a batteryStart-up of an inverter Frequency converter or multi-bypass UPSShutdown of an inverter ShutdownShutdown of a unit Shutdown of an rectifier/chargerSingle-unit or single modular External maintenance bypassSystem shutdown Modular UPSNo Mains Buzzer resetParallel UPSs with SSC With MainsAlarms Maintenance bypassEnvironment information Signal receptionSignal transmission Standard information Media ContactsLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Display of voltage measurements Voltage measurementsCurrent measurements Display of current measurementsDisplay of power and frequency measurements Frequency and power measurementsBattery measurements Display of battery measurementsBattery test see figure opposite Display for the inverter On/Off commands Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display of the settings selection screensDisplay system configuration Display system configurationMedia Contacts 15 additional auxiliary transmission LED signalling boxOptions Tele-Monitor remote indications unitHarmonics filter and power factor improvement Vision displayRemote vision display Empty cubicles Battery Temperature MonitorDouble bridge rectifier-charger Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC