Control panel (cont.)
"Inverter off" button
! | ! | + – | I | O |
7
This gray button 7 turns the inverter off.
◗press the "inverter off" button 7 for
3 seconds;
◗if the transfer to Mains 2 conditions are correct:
◗the load is transferred without interrupting to Mains 2,
◗the inverter shuts down,
◗ the green "load protected" light 5 goes off and the red "load not protected" light 2 goes on.
◗if the transfer to Mains 2 conditions are not correct, the button produces no effect. A special function on the hidden panel may be used to force the transfer.
Caution:
If the transfer is forced, the load will be subjected to a 0.8 second interruption in the supply of power.
Note:
◗for Modular UPSs or parallel UPSs with SSC, the shutdown of an inverter may or may not result in the transfer of the load to Mains 2, depending on redundancy conditions;
◗if the transfer to Mains 2 conditions are not correct or if the system does not have a Mains 2, the shutdown of a single inverter will result in the shutdown of the entire system if there is no redundancy.
Hidden control panel
The hidden panel, located behind the hinged cover, offers the following indications and control functions:
◗environment faults;
◗general faults in system modules;
◗special control buttons
(see figure 28).
This panel is identical for all types of cubicles, however, the controls or indications 8 that do not concern a given cubicle are not activated.
Clear fault log
This button 10 clears the alarms stored in memory. The memory may not be cleared until the cause of the alarms has ceased.
Hidden control panel (Inverter and Static Switch Cubicles)
|
|
|
|
|
| 8 |
|
|
|
|
| A B C D E F G H I J K L M N | |||||
| fault |
| 1 | 2 |
| 3 | 4 | 5 |
9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 |
Fig. 28
Buzzer reset
This button 11 stops the buzzer. A new fault starts the buzzer again.
Battery charge cycle
This button 12 starts a battery charge cycle (vented
Return to float charge
This button 13 can be used during a charge cycle to force the RC to return to "floating" mode.
Security button
This button 14 avoids inadvertent operation of the remaining three control buttons:
◗Mains 2 synchronization or desynchronization;
◗forced transfer to inverter with load interruption;
Page 18 - 6739380EN/JC
◗forced inverter shutdown with load interruption;
When pressing one of the above three buttons, the security button must also be pressed at the same time.
Mains 2 synchronization or desynchronization
This button 15 desynchronizes or resynchronizes the inverter output frequency with that of Mains 2.
Note:
◗for
Forced transfer to inverter with load interruption
This button 16 transfers the load to the inverter. If the transfer conditions (Mains 2 characteristics outside tolerances) are not correct, the transfer will result in a 0.8 second interruption in the supply of power to the load.
Note:
◗for
◗for parallel UPSs with centralised SSC, this function is available only on the SSC.
Forced inverter shutdown with load interruption
This button 17 :
◗transfers the load to Mains 2;
◗shuts down the inverter.
It may be used if the transfer conditions (Mains 2 characteristics outside tolerances) are not correct, in which case the "inverter off" button 7 on the visible control panel produces no effect;
◗is disabled on the SSC.