APC 6739380EN/JC LED signalling box optional, Additional information Media Contacts 15 optional

Page 29

Environment information (cont.)

"LED" signalling box (optional)

A basic "LED" signalling box with four indication lights may be supplied as an option with the MGETM GalaxyTM 6000 system.

It supplies the following signals:

load on battery;

low battery shutdown warning; inverter stop;

general alarm.

It connects to the terminals presented on the preceding page and draws its power from the external 220V AC, 50Hz or 60Hz power supply not connected to a UPS.

Additional information "Media Contacts 15" (optional)

An additional board may be installed in all types of systems. Terminals XR5 to XR9 on the board may be used to receive additional information from the environment and supply more precise information on system status (see figures 18, 19, 20 and 22 for the position of the board).

Additional remote transmission board

XR8 XR9 XR5 XR6 XR7

Signal reception

The signals should be provided by volt- free contacts.

"desynchronization with Mains 2" signal inhibits the inverter from synchronizing its output frequency with that of Mains 2. The inverter supplies a stable frequency and the load may no longer be correctly transferred from the inverter to Mains 2. In the event of a malfunction or an overload, the transfer will take place with a 0.8 second interruption in the supply of power to the load;

"gradual rectifier/charger shutdown" signal makes the rectifier/ charger shut down progressively to avoid excessive step load variations in the event of a low output engine generator set replacing Mains 1;

"generator current limiting" signal makes the rectifier/charger current limit the power drawn when a low output engine generator set has replaced Mains 1. The additional power required for the inverter is supplied by the battery;

"battery charge current limiting" signal reduces the battery charge current (programmable parameter) in the event a low output engine generator set has replaced Mains 1;

"transfer to Mains 2 disabled" signal blocks transfer of the load from the inverter to Mains 2. In the event the inverter shuts down (overload, etc.), the load is no longer supplied (for modular UPSs, this information is disabled and transferred to an auxiliary output);

"transfer to Mains 2 with interruption disabled" signal blocks transfer of the load from the inverter to Mains 2 if it would result in an interruption in the supply of power to the load. Only no-break transfers are allowed, i.e. transfer to Mains 2 conditions must be correct or the transfer is disabled (for modular UPSs, this information is disabled and transferred to an auxiliary output);

"auxiliary" signal can be used to provoke (depending on personalization):

a forced shutdown of the inverter (regardless of the status of Mains 2),

a protected inverter shutdown (transfer of the load to Mains 2 without interruption only if it is within tolerances),

modification of the inverter output frequency (50Hz or 60Hz);

"remote inverter on" signal can be used to remotely start the inverter;

"remote inverter off" signal can be used to remotely shut down the inverter.

Note:

In a system with a Static Switch Cubicle, the following signals must be directed to the Static Switch Cubicle:

desynchronization with Mains 2,

transfer to Mains 2 disabled,

transfer to Mains 2 with interruption disabled.

6739380EN/JC - Page 29

Image 29
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System performance IntroductionSystem description System may also includeUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure UPS or converter cubicles Static Switch CubicleIsolation and protection devices Operation with Mains 1 down Main operating modesNormal operation Battery charge cycle Battery timeOperation with Mains 1 restored UPS shutdown or overload Installation with an engine generator setExample of an installation with an engine generator set Frequency converters without redundancy Output voltage quality and continuityFrequency converters with redundancy Overload curveInverter cubicle Description of MGETMGalaxyTM 6000 cubicles250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterFor a 250 to 300kVA UPS Battery cubicleKVA UPS External maintenance bypass cubicle Static Switch CubicleControl panel Visible control panel Static Switch CubicleVisible control panel Mgetm GalaxyTM 6000 control panelBattery operation light Buzzer Operating problem lightLoad not protected light Load protected lightHidden control panel Light G battery charging Light F battery temperature outside tolerancesLight H inverter fault Light I battery dischargedSystem start-up Start-upSingle-unit or modular UPS Multi-bypass modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a unit Parallel UPS systems with a Static Switch CubicleFrequency converters Start-up of a rectifier/chargerStart-up of an inverter Frequency converter without a batterySingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown of a unit ShutdownShutdown of an inverter Shutdown of an rectifier/chargerSystem shutdown External maintenance bypassSingle-unit or single modular Modular UPSParallel UPSs with SSC Buzzer resetNo Mains With MainsMaintenance bypass AlarmsSignal transmission Signal receptionEnvironment information Standard information Media ContactsAdditional remote transmission board LED signalling box optionalAdditional information Media Contacts 15 optional 30 6739380EN/JC Single-unit or single modular UPS figure MaintenanceMaintenance configuration Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceFunctional check AutodiagnosticsVisual check Training centers Display Monitor alphanumeric displayGeneral Red lights Lights 1 toGreen lights Display of alarms Alarm display and buzzer resetList of general alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Current measurements Voltage measurementsDisplay of voltage measurements Display of current measurementsBattery measurements Frequency and power measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Language, display contrast and buzzer volume settings Inverter On/Off commandsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationOptions LED signalling boxMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitRemote vision display Harmonics filter and power factor improvementVision display Double bridge rectifier-charger Battery Temperature MonitorEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC