APC 6739380EN/JC user manual Isolation and protection devices, UPS or converter cubicles

Page 8

Introduction (cont.)

Isolation and protection devices

UPS or converter cubicles

(figure 8)

Q1 (switch):

isolation from Mains 1,

RC start-up;

QF1 (circuit breaker):

battery protection and isolation;

Q5N (switch):

isolation of the inverter, frequency converter or static switch module from the load;

Q4S (switch):

isolation of the static switch from Mains 2;

Q3BP (switch):

bypass switch for maintenance;

FU1-2-3 (fuses):

protection of the RC from Mains 1;

FU5-6-7 (fuses):

protection of the inverter from the load.

Note:

switches Q4S and Q3BP do not exist on frequency converters,

circuit breaker QF1 does not exist on frequency converters without a battery.

Example of a single-unit UPS or single modular UPS

Q3BP

 

 

 

 

 

Q4S

static switch

mains 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rectifier-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inverter

 

 

 

charger

 

 

 

 

 

Q1

 

 

 

 

 

 

 

 

 

 

 

Q5N

 

 

 

 

 

 

 

 

 

 

 

mains 1

 

 

 

 

 

 

 

 

 

 

 

 

 

load

FU1-2-3

 

 

QF1

 

 

 

FU5-6-7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 8

Static Switch Cubicle

 

 

 

 

 

 

 

 

 

(figure 9)

 

 

 

 

 

 

 

 

Q3BP

Q4S (switch):

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isolation of the static switch (and

 

 

 

 

 

 

 

 

 

mechanical contactor K2S) from

 

 

static switch

Mains 2;

 

 

 

 

Q4S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q3BP (switch):

mains 2

 

 

 

 

 

 

 

bypass switch for maintenance;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Q5N (switch):

 

 

 

 

 

 

 

 

 

isolation of the load from the parallel

 

 

 

 

 

 

 

 

Q5N

UPSs;

parallel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load

Q1 (fuse switch):

UPSs

 

 

 

 

 

 

 

protection of the cubicle control

 

Q2

 

 

 

 

 

 

 

electronics from the parallel-connected

 

Q1

 

control

inverter outputs;

 

 

 

electronics

 

 

 

 

 

 

 

 

 

Q2 (fuse switch):

protection of the cubicle control

electronics from Mains 2.

Fig. 9

 

 

External maintenance bypass cubicle (figure 10)

Q3BP (switch):

bypass switch for maintenance;

Q5N (switch):

isolation of the load from the parallel- connected UPSs.

Q3BP

maintenance bypass line

 

Q5N

parallel

load

modular UPSs

 

Fig. 10

Page 8 - 6739380EN/JC

Image 8
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options Introduction System performanceSystem description System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure UPS or converter cubicles Static Switch CubicleIsolation and protection devices Operation with Mains 1 down Main operating modesNormal operation Battery charge cycle Battery timeOperation with Mains 1 restored UPS shutdown or overload Installation with an engine generator setExample of an installation with an engine generator set Output voltage quality and continuity Frequency converters without redundancyFrequency converters with redundancy Overload curveDescription of MGETMGalaxyTM 6000 cubicles Inverter cubicle250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterFor a 250 to 300kVA UPS Battery cubicleKVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Static Switch Cubicle Control panelVisible control panel Mgetm GalaxyTM 6000 control panelBuzzer Operating problem light Battery operation lightLoad not protected light Load protected lightHidden control panel Light F battery temperature outside tolerances Light G battery chargingLight H inverter fault Light I battery dischargedStart-up System start-upSingle-unit or modular UPS Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSParallel UPS systems with a Static Switch Cubicle Start-up of a unitFrequency converters Start-up of a rectifier/chargerFrequency converter without a battery Start-up of an inverterSingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown Shutdown of a unitShutdown of an inverter Shutdown of an rectifier/chargerExternal maintenance bypass System shutdownSingle-unit or single modular Modular UPSBuzzer reset Parallel UPSs with SSCNo Mains With MainsAlarms Maintenance bypassSignal reception Signal transmissionEnvironment information Standard information Media ContactsAdditional remote transmission board LED signalling box optionalAdditional information Media Contacts 15 optional 30 6739380EN/JC Single-unit or single modular UPS figure MaintenanceMaintenance configuration Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesFunctional check AutodiagnosticsVisual check Training centers Display Monitor alphanumeric displayGeneral Red lights Lights 1 toGreen lights Display of alarms Alarm display and buzzer resetList of general alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Voltage measurements Current measurementsDisplay of voltage measurements Display of current measurementsFrequency and power measurements Battery measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Inverter On/Off commands Language, display contrast and buzzer volume settingsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationLED signalling box OptionsMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitRemote vision display Harmonics filter and power factor improvementVision display Battery Temperature Monitor Double bridge rectifier-chargerEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC