Introduction (cont.)
Isolation and protection devices
UPS or converter cubicles
(figure 8)
◗Q1 (switch):
◗isolation from Mains 1,
◗RC
◗QF1 (circuit breaker):
◗battery protection and isolation;
◗Q5N (switch):
◗isolation of the inverter, frequency converter or static switch module from the load;
◗Q4S (switch):
◗isolation of the static switch from Mains 2;
◗Q3BP (switch):
◗bypass switch for maintenance;
◗
◗protection of the RC from Mains 1;
◗FU5-6-7 (fuses):
◗protection of the inverter from the load.
Note:
◗switches Q4S and Q3BP do not exist on frequency converters,
◗circuit breaker QF1 does not exist on frequency converters without a battery.
Example of a
Q3BP
|
|
|
|
| Q4S | static switch | ||||||||
mains 2 |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |||||
|
|
| rectifier- |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| inverter | ||||||
|
|
| charger |
|
|
|
|
| ||||||
Q1 |
|
|
|
|
|
|
|
|
|
|
| Q5N | ||
|
|
|
|
|
|
|
|
|
|
| ||||
mains 1 |
|
|
|
|
|
|
|
|
|
|
|
|
| load |
|
| QF1 |
|
|
| |||||||||
|
|
|
|
| ||||||||||
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
| battery | |||||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Fig. 8
Static Switch Cubicle |
|
|
|
|
|
|
|
|
|
(figure 9) |
|
|
|
|
|
|
|
| Q3BP |
◗ Q4S (switch): |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
◗ isolation of the static switch (and |
|
|
|
|
|
|
|
|
|
mechanical contactor K2S) from |
|
| static switch | ||||||
Mains 2; |
|
| |||||||
|
| Q4S |
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
◗ Q3BP (switch): | mains 2 |
|
|
|
|
|
|
| |
◗ bypass switch for maintenance; |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| |
◗ Q5N (switch): |
|
|
|
|
|
|
|
|
|
◗ isolation of the load from the parallel |
|
|
|
|
|
|
|
| Q5N |
UPSs; | parallel |
|
|
|
|
|
|
| |
|
|
|
|
|
|
| load | ||
◗ Q1 (fuse switch): | UPSs |
|
|
|
|
|
|
| |
◗ protection of the cubicle control |
| Q2 |
|
|
|
|
|
|
|
electronics from the |
| Q1 |
| control | |||||
inverter outputs; |
|
|
| electronics | |||||
|
|
|
|
|
|
|
|
|
◗Q2 (fuse switch):
◗protection of the cubicle control
electronics from Mains 2. | Fig. 9 |
|
|
External maintenance bypass cubicle (figure 10)
◗Q3BP (switch):
◗bypass switch for maintenance;
◗Q5N (switch):
◗isolation of the load from the parallel- connected UPSs.
Q3BP
maintenance bypass line
| Q5N |
parallel | load |
modular UPSs |
|
Fig. 10
Page 8 - 6739380EN/JC