APC 6739380EN/JC Maintenance configuration, Single-unit or single modular UPS figure

Page 31

Maintenance

Maintenance configuration

Single-unit or single modular UPS (figure 29)

During maintenance, the UPS must be isolated from Mains 1 and 2, the battery and the load.

inverter isolation

Proceed in the following order:

shut down the inverter (press the "inverter off" button 7 for 3 seconds),

close bypass switch Q3BP,

open isolating switches Q5N, Q4S, QF1 and Q1.

The UPS is powered down once the capacitors have discharged (a few minutes);

start-up

mains 2

Q1

mains 1

Q3BP

static switch

Q4S

rectifier-

chargerinverter

Q5N

load

QF1

battery

Following servicing, proceed in the following order:

close switch Q1, then after approximately ten seconds, switches QF1, Q5N and Q4S,

open bypass switch Q3BP,

start the inverter (press the "inverter on" button 6 ).

Fig. 29

 

Caution:

to avoid interrupting the load, the

work should be carried out in

various switching operations must

accordance with applicable safety

be carried out in the correct order.

regulations;

Operations are explained in

 

diagrams placed next to the

 

switches.

Multi-bypass modular UPS

(figure 30)

Prior to servicing a given UPS, it must be isolated from Mains 1, Mains 2, its

Modular UPS 1

Q3BP

 

battery and the load outputs of the other UPSs (in this case, never operate the Q3BP switches in the units).

isolate the UPS

Proceed in the following order:

shut down the inverter (press the

"inverter off" button 7 for three

seconds);

open isolating switches Q5N, QF1,

Q4S and Q1 in the unit.

The UPS is de-energised once the

capacitors have discharged (a few

mains 2

Q1

mains 1

static switch

Q4S

rectifier-

chargerinverter

Q5N

QF1

battery

minutes).

start-up

Once servicing is completed, proceed in the following order:

close Q1, then QF1, Q4S and Q5N;

start the inverter (press the “inverter on” button 6 ).

Note. It is strongly advised to call on our after-sales support department for these operations.

Modular UPS 2

mains 2

rectifier- charger

Q1

mains 1

Q4S

QF1

Q3BP

load

static switch

inverter

Q5N

battery

Fig. 30

6739380EN/JC - Page 31

Image 31
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System may also include IntroductionSystem performance System descriptionUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Overload curve Output voltage quality and continuityFrequency converters without redundancy Frequency converters with redundancy450 to 500kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 250 to 400kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleMgetm GalaxyTM 6000 control panel Visible control panel Static Switch CubicleControl panel Visible control panelLoad protected light Buzzer Operating problem lightBattery operation light Load not protected lightHidden control panel Light I battery discharged Light F battery temperature outside tolerancesLight G battery charging Light H inverter faultMulti-bypass modular UPS Start-upSystem start-up Single-unit or modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a rectifier/charger Parallel UPS systems with a Static Switch CubicleStart-up of a unit Frequency convertersFrequency converter or multi-bypass UPS Frequency converter without a batteryStart-up of an inverter Single-unit or modular UPS systemShutdown of an rectifier/charger ShutdownShutdown of a unit Shutdown of an inverterModular UPS External maintenance bypassSystem shutdown Single-unit or single modularWith Mains Buzzer resetParallel UPSs with SSC No MainsMaintenance bypass AlarmsStandard information Media Contacts Signal receptionSignal transmission Environment informationAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Display of current measurements Voltage measurementsCurrent measurements Display of voltage measurementsDisplay of battery measurements Frequency and power measurementsBattery measurements Display of power and frequency measurementsBattery test see figure opposite Display of the settings selection screens Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display for the inverter On/Off commandsDisplay system configuration Display system configurationTele-Monitor remote indications unit LED signalling boxOptions Media Contacts 15 additional auxiliary transmissionVision display Harmonics filter and power factor improvementRemote vision display Mgetm GalaxyTM 6000UPSs standard input rectifier-charger Battery Temperature MonitorDouble bridge rectifier-charger Empty cubicles50 6739380EN/JC