APC 6739380EN/JC Start-up of a unit, Frequency converters, Start-up of a rectifier/charger

Page 22

Start-up (cont.)

Frequency converters

Proceed in the following order:

check that all lines supplying the load are off or that the load is disconnected;

close the upstream switch supplying Mains 1 power (on the LV switchboard);

close Mains 1 input switch Q1.

The system powers up:

Q1

 

Q5N

OFF

ON

OFF

(0)

(I)

(0)

 

red "load not protected" light 2 on the control panel goes on,

the rectifier-charger automatically starts;

close battery circuit breaker QF1 (systems equipped with a battery);

QF1

OFF

ON

(0)

(I)

close inverter output switch Q5N:

Q1

Q5N

ON

OFF

ON

 

 

(I)

(0)

(I)

 

press the "inverter on" button 6 on the control panel:

!

!

+ –

I

O

 

 

 

 

6

 

green "load protected" light 5 blinks for 3 seconds,

the inverter starts and awaits the start of the other inverters;

proceed in the same manner for each line;

when they are all on or enough have been started to supply the rated load, the output switch for each running line closes. The load is supplied and the connected devices can be started,

red "load not protected" light 2 goes off,

green "load protected" light 5 remains constant, on the control panel of each line supplying the load.

Parallel UPS systems with a Static Switch Cubicle

Proceed in the following order:

check that all lines supplying the load are off or that the load is disconnected;

close the upstream switches supplying Mains 1 and 2 power (on the LV switchboard);

close fuse switch Q2 in the Static Switch Cubicle (see figure 22);

close Mains 2 input switch Q4S in the Static Switch Cubicle;

close switch Q5N in the Static Switch Cubicle;

open maintenance bypass switch Q3BP in the Static Switch Cubicle;

close fuse switch Q1 in the Static Switch Cubicle;

close input switch Q1 on an UPS line.

The line powers up;

red "load not protected" light 2 on the line control panel goes on,

the RC automatically starts;

close the line battery circuit breaker QF1;

close inverter output switch Q5N for the line;

press the "inverter on" button 6 on the line control panel;

green "load protected" light 5 blinks for 3 seconds,

the inverter starts and awaits the start of the other inverters;

proceed in the same manner for each line;

when they are all on or enough have been started to supply the rated load power, the output switch for each running line closes and the load is supplied with power;

red "load not protected" light 2 goes off,

green "load protected" light 5 remains on, without blinking, on the control panel of each line supplying the load.

Start-up of a unit

Start-up of a rectifier/charger

it is recommended not to stop the rectifier/charger because the battery will no longer be charged. Rectifier/ charger start-up is automatic when Mains 1 input switch Q1 is closed;

red "load not protected" light 2 on the control panel goes on;

close battery circuit breaker QF1.

Page 22 - 6739380EN/JC

Image 22
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System description IntroductionSystem performance System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Frequency converters with redundancy Output voltage quality and continuityFrequency converters without redundancy Overload curve250 to 400kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 450 to 500kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Visible control panel Static Switch CubicleControl panel Mgetm GalaxyTM 6000 control panelLoad not protected light Buzzer Operating problem lightBattery operation light Load protected lightHidden control panel Light H inverter fault Light F battery temperature outside tolerancesLight G battery charging Light I battery dischargedSingle-unit or modular UPS Start-upSystem start-up Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSFrequency converters Parallel UPS systems with a Static Switch CubicleStart-up of a unit Start-up of a rectifier/chargerSingle-unit or modular UPS system Frequency converter without a batteryStart-up of an inverter Frequency converter or multi-bypass UPSShutdown of an inverter ShutdownShutdown of a unit Shutdown of an rectifier/chargerSingle-unit or single modular External maintenance bypassSystem shutdown Modular UPSNo Mains Buzzer resetParallel UPSs with SSC With MainsAlarms Maintenance bypassEnvironment information Signal receptionSignal transmission Standard information Media ContactsAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Display of voltage measurements Voltage measurementsCurrent measurements Display of current measurementsDisplay of power and frequency measurements Frequency and power measurementsBattery measurements Display of battery measurementsBattery test see figure opposite Display for the inverter On/Off commands Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display of the settings selection screensDisplay system configuration Display system configurationMedia Contacts 15 additional auxiliary transmission LED signalling boxOptions Tele-Monitor remote indications unitVision display Harmonics filter and power factor improvementRemote vision display Empty cubicles Battery Temperature MonitorDouble bridge rectifier-charger Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC