APC 6739380EN/JC user manual Buzzer reset, Parallel UPSs with SSC, No Mains, With Mains

Page 26

Shutdown (cont.)

Multi-bypass modular UPS

shutdown each UPS (see section "shutdown of a unit");

the load is supplied via the Mains 2 of each UPS;

close switch Q3BP on each UPS, the load is supplied by the Mains 2, via the bypass lines (Q3BP) of each UPS;

open switches Q5N, Q4S, Q1 and QF1 on each UPS, the situation is that shown in the figure opposite;

the UPSs are de-energised once the capacitors have discharged.

Modular UPS 1

Q3BP

 

 

static switch

 

 

Q4S

 

rectifier-

inverter

 

charger

 

Q1

Q5N

 

mains 1

 

 

 

QF1

 

mains 2

battery

 

Modular UPS 2

Q3BP

load

 

 

 

 

static switch

 

 

Q4S

 

rectifier-

inverter

 

charger

 

Q1

Q5N

 

mains 1

 

 

 

QF1

 

 

battery

 

Frequency converters

(no Mains 2)

Shutdown of the inverters results in the interruption of the load;

shut down each inverter (see the "shutdown of a unit" section);

open battery circuit breaker QF1 and Mains 1 input switch Q1 on each unit;

QF1

ON OFF

(I)

(0)

Q1

ON OFF

(I)

(0)

Q5N

ON

(I)

the system is powered down (except the Mains 1 cables upstream from switch Q1). A full powering down requires the opening of the upstream protection device on Mains 1.

Parallel UPSs with SSC

(with Mains 2)

shut down each inverter (see the "shutdown of a unit" section);

carry out the maintenance bypass operation in the Static Switch Cubicle (the load will be directly supplied by Mains 2 via maintenance bypass switch Q3BP);

close switch Q3BP and open switches Q5N and Q4S in the "static switch" cubicle;

open fuse switches Q1 and Q2 in the Static Switch Cubicle;

open battery circuit breaker QF1 in each UPS (except for frequency converters without a battery);

open input switch Q1 for each UPS;

the UPSs are powered down (except

the Mains cables upstream from switches Q1, Q4S and Q3BP) and the load is supplied by Mains 2.

All the lights on the control panel are off. A full powering down requires load shutdown and the opening of the upstream protection devices on Mains 1 and 2.

Buzzer reset

first determine the cause of the alarm;

press the "buzzer reset" button 11 on the hidden control panel on the concerned cubicle.

The buzzer stops, but a new alarm will set it off again.

A B C D E F G H I J K L M N

1

2

3

4

5

11

Page 26 - 6739380EN/JC

Image 26
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System description IntroductionSystem performance System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure UPS or converter cubicles Static Switch CubicleIsolation and protection devices Operation with Mains 1 down Main operating modesNormal operation Battery charge cycle Battery timeOperation with Mains 1 restored UPS shutdown or overload Installation with an engine generator setExample of an installation with an engine generator set Frequency converters with redundancy Output voltage quality and continuityFrequency converters without redundancy Overload curve250 to 400kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 450 to 500kVA UPS or frequency converterFor a 250 to 300kVA UPS Battery cubicleKVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Visible control panel Static Switch CubicleControl panel Mgetm GalaxyTM 6000 control panelLoad not protected light Buzzer Operating problem lightBattery operation light Load protected lightHidden control panel Light H inverter fault Light F battery temperature outside tolerancesLight G battery charging Light I battery dischargedSingle-unit or modular UPS Start-upSystem start-up Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSFrequency converters Parallel UPS systems with a Static Switch CubicleStart-up of a unit Start-up of a rectifier/charger Single-unit or modular UPS system Frequency converter without a battery Start-up of an inverter Frequency converter or multi-bypass UPSShutdown of an inverter ShutdownShutdown of a unit Shutdown of an rectifier/chargerSingle-unit or single modular External maintenance bypassSystem shutdown Modular UPSNo Mains Buzzer resetParallel UPSs with SSC With MainsAlarms Maintenance bypassEnvironment information Signal receptionSignal transmission Standard information Media ContactsAdditional remote transmission board LED signalling box optionalAdditional information Media Contacts 15 optional 30 6739380EN/JC Single-unit or single modular UPS figure MaintenanceMaintenance configuration Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesFunctional check AutodiagnosticsVisual check Training centers Display Monitor alphanumeric displayGeneral Red lights Lights 1 toGreen lights Display of alarms Alarm display and buzzer resetList of general alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Display of voltage measurements Voltage measurementsCurrent measurements Display of current measurementsDisplay of power and frequency measurements Frequency and power measurementsBattery measurements Display of battery measurementsBattery test see figure opposite Display for the inverter On/Off commands Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display of the settings selection screensDisplay system configuration Display system configurationMedia Contacts 15 additional auxiliary transmission LED signalling boxOptions Tele-Monitor remote indications unitRemote vision display Harmonics filter and power factor improvementVision display Empty cubicles Battery Temperature MonitorDouble bridge rectifier-charger Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC