APC 6739380EN/JC Start-up, System start-up, Single-unit or modular UPS, Multi-bypass modular UPS

Page 20

Start-up

System start-up

Single-unit or modular UPS

Proceed in the following order:

close the upstream switches supplying Mains 1 and 2 power (on the LV switchboard);

close Mains 1 input switch Q1.

The system powers up:

Q1 Q4S Q3BP Q5N

OFF

ON

OFF

ON

OFF

(0)

(I)

(0)

(I)

(0)

 

 

 

red "load not protected" light 2 on the control panel goes on,

the rectifier/chargers automatically starts;

close Mains 2 input Q4S:

Q1 Q4S Q3BP Q5N

ON

OFF

ON

ON

OFF

 

 

(I)

(0)

(I)

(I)

(0)

 

 

 

close inverter output switch Q5N:

Q1 Q4S Q3BP Q5N

ON

ON

ON

OFF

ON

(I)

(I)

(I)

(0)

(I)

 

 

 

close battery circuit breaker QF1:

QF1

OFF

ON

(0)

(I)

open maintenance bypass switch Q3BP:

Q1 Q4S Q3BP Q5N

ON

ON

ON OFF

ON

(I)

(I)

(I)

(0)

(I)

 

 

 

press the inverter on button 6 on the control panel:

!

!

+ –

I

O

 

 

 

 

6

 

green "load protected" light 5 blinks for 3 seconds,

the inverter starts and if transfer to

Mains 2 conditions are correct, the load is supplied by the inverter,

red "load not protected" light 2 goes off,

green "load protected" light 5 remains on, without blinking.

Multi-bypass modular UPS

Proceed in the following order:

check that switches Q1, Q4S, Q5N and QF1 on the UPSs are open and that switches Q3BP are closed, otherwise set them to the required position;

close the upstream switches (on the low-voltage switchboard) supplying power to the Mains 1 and Mains 2 inputs on the UPSs, the load is supplied with power;

close the Mains 1 input switch Q1 on the UPSs to supply them with power:

Q1 Q4S Q3BP Q5N

OFF

ON

OFF

ON

OFF

(0)

(I)

(0)

(I)

(0)

 

 

 

red "load not protected" light 2 on the control panels of the UPSs goes on:

!

!

+ –

I

O

 

 

 

 

2

the rectifier/chargers automatically start;

close the Mains 2 input switch Q4S on the UPSs:

Q1 Q4S Q3BP Q5N

ON

OFF

ON

ON

OFF

(I)

(0)

(I)

(I)

(0)

 

 

 

close inverter output switch Q5N on the UPSs:

Q1

Q4S

Q3BP

Q5N

ON

ON

ON

OFF

ON

(I)

(I)

(I)

(0)

(I)

 

 

 

close battery circuit breaker QF1 on the UPSs:

QF1

OFF

ON

(0)

(I)

open maintenance bypass switch Q3BP on the UPSs:

Q1 Q4S Q3BP Q5N

ON

ON

ON OFF

ON

(I)

(I)

(I)

(0)

(I)

 

 

 

the load is now supplied by the Mains 2 input via the static switches of the UPSs.

press the "inverter on" button 6 on the control panel of each UPSs:

!

!

+ –

I

O

 

 

 

 

6

 

green "load protected" light 5 flashes for three seconds,

the inverter starts and, if transfer conditions with the Mains 2 input are correct, the load is transferred to the inverter,

red "load not protected" light 2 goes off,

green "load protected" light 5 on the control panel goes on.

Page 20 - 6739380EN/JC

Image 20
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options Introduction System performanceSystem description System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure UPS or converter cubicles Static Switch CubicleIsolation and protection devices Operation with Mains 1 down Main operating modesNormal operation Battery charge cycle Battery timeOperation with Mains 1 restored UPS shutdown or overload Installation with an engine generator setExample of an installation with an engine generator set Output voltage quality and continuity Frequency converters without redundancyFrequency converters with redundancy Overload curveDescription of MGETMGalaxyTM 6000 cubicles Inverter cubicle250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterFor a 250 to 300kVA UPS Battery cubicleKVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Static Switch Cubicle Control panelVisible control panel Mgetm GalaxyTM 6000 control panelBuzzer Operating problem light Battery operation lightLoad not protected light Load protected lightHidden control panel Light F battery temperature outside tolerances Light G battery chargingLight H inverter fault Light I battery dischargedStart-up System start-upSingle-unit or modular UPS Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSParallel UPS systems with a Static Switch Cubicle Start-up of a unitFrequency converters Start-up of a rectifier/chargerFrequency converter without a battery Start-up of an inverterSingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown Shutdown of a unitShutdown of an inverter Shutdown of an rectifier/chargerExternal maintenance bypass System shutdownSingle-unit or single modular Modular UPSBuzzer reset Parallel UPSs with SSCNo Mains With MainsAlarms Maintenance bypassSignal reception Signal transmissionEnvironment information Standard information Media ContactsAdditional remote transmission board LED signalling box optionalAdditional information Media Contacts 15 optional 30 6739380EN/JC Single-unit or single modular UPS figure MaintenanceMaintenance configuration Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesFunctional check AutodiagnosticsVisual check Training centers Display Monitor alphanumeric displayGeneral Red lights Lights 1 toGreen lights Display of alarms Alarm display and buzzer resetList of general alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Voltage measurements Current measurementsDisplay of voltage measurements Display of current measurementsFrequency and power measurements Battery measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Inverter On/Off commands Language, display contrast and buzzer volume settingsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationLED signalling box OptionsMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitRemote vision display Harmonics filter and power factor improvementVision display Battery Temperature Monitor Double bridge rectifier-chargerEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC