APC 6739380EN/JC user manual Main operating modes, Normal operation, Operation with Mains 1 down

Page 9

Main operating modes

Normal operation

Mains 1 power is available: (see figure 11).

The green "load protected" light 5 on the control panel is on.

!

!

+ –

I

O

 

 

 

5

 

légend :

 

off

on

 

Introduction (cont.)

static switch

mains 2

rectifier-

chargerinverter

mains 1

load

battery

The power necessary for the load is provided by Mains 1 through the rectifier-charger and the inverter.

The rectifier-charger also supplies the power to float charge and recharge the battery (1). The rectifier-charger output voltage (DC) is regulated for the different battery types and charging modes:

vented lead-acid or Ni/Cd batteries: two different voltages, one for float charging and one for recharging;

sealed lead-acid batteries: a single voltage for both charge functions.

Operation with Mains 1 down

Fig. 11

The voltages depend on the number of battery cells and the battery manufacturer. They can be factory set and are adjustable by the after-sales support technicians.

An optional electronic board may be used to continuously measure the battery temperature and automatically adjust the voltages.

Parallel UPS systems:

the power drawn by the load is equally shared between the different UPSs.

(1)Except for frequency converters without a battery

(figure 12)

In the event of a Mains 1 failure or Mains 1 voltage outside specified tolerance of –10% in amplitude (–15% optionally), the rectifier-charger stops and the battery supplies the necessary backup power to the load via the inverter. The battery, float-connected between the rectifier-charger and the inverter, discharges during this operating mode.

The green "load protected" light 5 on the control panel is on.

The user is warned of battery operation by a buzzer and the orange "load on battery" light 4 on the control panel.

beep...beep...

!

!

+ –

I

O

45

 

static switch

mains 2

 

rectifier-

inverter

charger

mains 1

load

 

battery

Fig. 12

 

This information is also available via

Note:

volt-free changeover contacts for

In the event of a Mains 1 failure,

remote control devices.

frequency converters without a battery

In this case, there is a 30 seconds

shut down and the load is no longer

delay.

supplied.

6739380EN/JC - Page 9

Image 9
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System performance IntroductionSystem description System may also includeUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Frequency converters without redundancy Output voltage quality and continuityFrequency converters with redundancy Overload curveInverter cubicle Description of MGETMGalaxyTM 6000 cubicles250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleControl panel Visible control panel Static Switch CubicleVisible control panel Mgetm GalaxyTM 6000 control panelBattery operation light Buzzer Operating problem lightLoad not protected light Load protected lightHidden control panel Light G battery charging Light F battery temperature outside tolerancesLight H inverter fault Light I battery dischargedSystem start-up Start-upSingle-unit or modular UPS Multi-bypass modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a unit Parallel UPS systems with a Static Switch CubicleFrequency converters Start-up of a rectifier/chargerStart-up of an inverter Frequency converter without a batterySingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown of a unit ShutdownShutdown of an inverter Shutdown of an rectifier/chargerSystem shutdown External maintenance bypassSingle-unit or single modular Modular UPSParallel UPSs with SSC Buzzer resetNo Mains With MainsMaintenance bypass AlarmsSignal transmission Signal receptionEnvironment information Standard information Media ContactsLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Current measurements Voltage measurementsDisplay of voltage measurements Display of current measurementsBattery measurements Frequency and power measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Language, display contrast and buzzer volume settings Inverter On/Off commandsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationOptions LED signalling boxMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitHarmonics filter and power factor improvement Vision displayRemote vision display Double bridge rectifier-charger Battery Temperature MonitorEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC