APC 6739380EN/JC Introduction, System performance, System description, System may also include

Page 5

Introduction

System performance

A MGETM GalaxyTM 6000

uninterruptible power supply (UPS)

delivers 3-phase power with the

following characteristics:

stable voltage (+/-0.5% under steady

Single-line diagram of the MGETM GalaxyTM 6000 system

state conditions and +/-5% under

transient conditions for load step

changes of 25 to 100% or of 100 to

25%);

stable frequency (+/-0.05Hz without

Mains 2);

or frequency synchronized with

Mains 2 to 50/60Hz +/-2Hz (value may

be configured in 0.25 HZ steps);

free of micro-breaks and outages for

the duration of the battery time (10, 15

or 30 minutes);

less than 4% distortion in all system

configurations with linear loads;

less than 5% distortion for a 100%

non-linear load with a peak factor of up

to 3.5.

The acoustic noise level of a

MGETM GalaxyTM 6000 UPS is under

70dBA.

mains 2 (bypass input)

mains 1 (normal input)

B

maintenance bypass

 

 

 

 

 

 

 

 

 

 

 

 

isolation

 

 

 

 

isolation

 

 

 

 

emergency

 

and

 

 

 

 

 

 

 

 

 

protection

 

 

 

 

 

 

 

 

bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isolation

AC/DC

 

 

DC/AC

 

 

 

 

and

conversion

 

 

conversion

 

 

 

 

protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isolation and

 

 

 

 

 

 

 

 

 

 

protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

battery

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

load

System description

a rectifier-charger (RC) module converts 3-phase AC power from the Mains 1 supply into DC power for the normal inverter input and float charges or recharges the batteries;

a battery unit provides backup power for the inverter in the event of a voltage drop or a Mains 1 failure;

an inverter module converts the DC power supplied by the rectifier-charger module or the battery unit into 3-phase AC power for the load;

an emergency bypass module ensures the instantaneous transfer of the load via the static switch to the Mains 2 bypass line in the event of an inverter shutdown (initiated by the user or by a protective device) or a sudden overload;

a maintenance bypass which isolates the UPS for maintenance and transfers the load without interrupting the supply of power. The maintenance bypass is made up of three manual switches.

Note:

the Mains 1 normal input and the Mains 2 bypass input have different functions and, depending on the installation, may be protected differently upstream and/or come from different sources;

frequency converters are available without backup batteries;

the emergency bypass line and the maintenance bypass line do not exist in installations where the load frequency and the Mains 2 frequency are different (for example in frequency converters);

for reasons of redundancy and/or increased power, the rectifier-charger, inverter and battery modules (the UPS, part A in the MGETM GalaxyTM 6000 schematic diagram above) may be arranged in parallel lines. In this case, an isolation function is added to the output of each UPS for maintenance without disrupting the load.

In this type of system, the components of part B in the diagram are located in a separate cubicle referred to as the "Static Switch Cubicle".

The system may also include:

an isolating transformer on the Mains 2 line;

a harmonics filter on the Mains 1 input;

different remote control, indication and display systems;

a double bridge rectifier-charger module.

6739380EN/JC - Page 5

Image 5
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System performance IntroductionSystem description System may also includeUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure UPS or converter cubicles Static Switch CubicleIsolation and protection devices Operation with Mains 1 down Main operating modesNormal operation Battery charge cycle Battery timeOperation with Mains 1 restored UPS shutdown or overload Installation with an engine generator setExample of an installation with an engine generator set Frequency converters without redundancy Output voltage quality and continuityFrequency converters with redundancy Overload curveInverter cubicle Description of MGETMGalaxyTM 6000 cubicles250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterFor a 250 to 300kVA UPS Battery cubicleKVA UPS External maintenance bypass cubicle Static Switch CubicleControl panel Visible control panel Static Switch CubicleVisible control panel Mgetm GalaxyTM 6000 control panelBattery operation light Buzzer Operating problem lightLoad not protected light Load protected lightHidden control panel Light G battery charging Light F battery temperature outside tolerancesLight H inverter fault Light I battery dischargedSystem start-up Start-upSingle-unit or modular UPS Multi-bypass modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a unit Parallel UPS systems with a Static Switch CubicleFrequency converters Start-up of a rectifier/chargerStart-up of an inverter Frequency converter without a batterySingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown of a unit ShutdownShutdown of an inverter Shutdown of an rectifier/chargerSystem shutdown External maintenance bypassSingle-unit or single modular Modular UPSParallel UPSs with SSC Buzzer resetNo Mains With MainsMaintenance bypass AlarmsSignal transmission Signal receptionEnvironment information Standard information Media ContactsAdditional remote transmission board LED signalling box optionalAdditional information Media Contacts 15 optional 30 6739380EN/JC Single-unit or single modular UPS figure MaintenanceMaintenance configuration Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceFunctional check AutodiagnosticsVisual check Training centers Display Monitor alphanumeric displayGeneral Red lights Lights 1 toGreen lights Display of alarms Alarm display and buzzer resetList of general alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Current measurements Voltage measurementsDisplay of voltage measurements Display of current measurementsBattery measurements Frequency and power measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Language, display contrast and buzzer volume settings Inverter On/Off commandsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationOptions LED signalling boxMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitRemote vision display Harmonics filter and power factor improvementVision display Double bridge rectifier-charger Battery Temperature MonitorEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC