Introduction
System performance
A MGETM GalaxyTM 6000 |
uninterruptible power supply (UPS) |
delivers |
following characteristics: |
◗ stable voltage |
Single-line diagram of the MGETM GalaxyTM 6000 system
state conditions and |
transient conditions for load step |
changes of 25 to 100% or of 100 to |
25%); |
◗ stable frequency |
Mains 2); |
◗ or frequency synchronized with |
Mains 2 to 50/60Hz |
be configured in 0.25 HZ steps); |
◗ free of |
the duration of the battery time (10, 15 |
or 30 minutes); |
◗ less than 4% distortion in all system |
configurations with linear loads; |
◗ less than 5% distortion for a 100% |
to 3.5. |
The acoustic noise level of a |
MGETM GalaxyTM 6000 UPS is under |
70dBA. |
mains 2 (bypass input)
mains 1 (normal input)
B
maintenance bypass
|
|
|
|
|
|
|
|
|
|
|
| isolation |
|
|
|
| isolation |
|
|
|
| emergency |
| and |
| ||
|
|
|
|
|
|
|
| protection |
| ||||
|
|
|
|
|
|
| bypass |
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| isolation | AC/DC |
|
| DC/AC |
|
|
| |||||
| and | conversion |
|
| conversion |
|
|
| |||||
| protection |
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
| isolation and |
|
|
|
| |||
|
|
|
|
|
| protection |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| battery |
|
|
|
|
| ||
| A |
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
load
System description
◗a
◗a battery unit provides backup power for the inverter in the event of a voltage drop or a Mains 1 failure;
◗an inverter module converts the DC power supplied by the
◗an emergency bypass module ensures the instantaneous transfer of the load via the static switch to the Mains 2 bypass line in the event of an inverter shutdown (initiated by the user or by a protective device) or a sudden overload;
◗a maintenance bypass which isolates the UPS for maintenance and transfers the load without interrupting the supply of power. The maintenance bypass is made up of three manual switches.
Note:
◗the Mains 1 normal input and the Mains 2 bypass input have different functions and, depending on the installation, may be protected differently upstream and/or come from different sources;
◗frequency converters are available without backup batteries;
◗the emergency bypass line and the maintenance bypass line do not exist in installations where the load frequency and the Mains 2 frequency are different (for example in frequency converters);
◗for reasons of redundancy and/or increased power, the
In this type of system, the components of part B in the diagram are located in a separate cubicle referred to as the "Static Switch Cubicle".
The system may also include:
◗an isolating transformer on the Mains 2 line;
◗a harmonics filter on the Mains 1 input;
◗different remote control, indication and display systems;
◗a double bridge
6739380EN/JC - Page 5