Environment information (cont.)

Signal transmission

These signals are each transmitted by two volt-free changeover contacts with a maximum breaking capacity of 5A 250V.

"overload" signal indicates that an overload has taken place (Pload > Pnominal in kVA);

"rectifier/charger function fault" signal indicates that:

a fault has taken place in the rectifier/charger module,

Mains 1 input switch Q1 is open;

"inverter function fault" signal indicates that a fault has taken place in the inverter module;

"transfer to inverter fault" signal indicates that the load transfer conditions from Mains 2 to the inverter are incorrect;

"transfer to Mains 2 fault" signal indicates that the transfer to Mains 2 conditions (voltage, frequency or phase) are incorrect and a forced transfer will result in a 0.8 second interruption in the supply of power to the load;

"rectifier/charger on" signal indicates the status of the module.

Note:

A Static Switch Cubicle receives only the following signals:

overload,

transfer to inverter fault,

transfer to Mains 2 fault.

Page 30 - 6739380EN/JC

Image 30
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System description IntroductionSystem performance System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Frequency converters with redundancy Output voltage quality and continuityFrequency converters without redundancy Overload curve250 to 400kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 450 to 500kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Visible control panel Static Switch CubicleControl panel Mgetm GalaxyTM 6000 control panelLoad not protected light Buzzer Operating problem lightBattery operation light Load protected lightHidden control panel Light H inverter fault Light F battery temperature outside tolerancesLight G battery charging Light I battery dischargedSingle-unit or modular UPS Start-upSystem start-up Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSFrequency converters Parallel UPS systems with a Static Switch CubicleStart-up of a unit Start-up of a rectifier/chargerSingle-unit or modular UPS system Frequency converter without a batteryStart-up of an inverter Frequency converter or multi-bypass UPSShutdown of an inverter ShutdownShutdown of a unit Shutdown of an rectifier/chargerSingle-unit or single modular External maintenance bypassSystem shutdown Modular UPSNo Mains Buzzer resetParallel UPSs with SSC With MainsAlarms Maintenance bypassEnvironment information Signal receptionSignal transmission Standard information Media ContactsLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Display of voltage measurements Voltage measurementsCurrent measurements Display of current measurementsDisplay of power and frequency measurements Frequency and power measurementsBattery measurements Display of battery measurementsBattery test see figure opposite Display for the inverter On/Off commands Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display of the settings selection screensDisplay system configuration Display system configurationMedia Contacts 15 additional auxiliary transmission LED signalling boxOptions Tele-Monitor remote indications unitHarmonics filter and power factor improvement Vision displayRemote vision display Empty cubicles Battery Temperature MonitorDouble bridge rectifier-charger Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC