Start-up (cont.)
Galaxy UPS 1
mains 2
rectifier- charger
Q1
mains 1
Q3BP
static switch
Q4S
inverter
Q5N
QF1
battery
load
Galaxy UPS 2 | Q3BP |
| |
| static switch |
| Q4S |
mains 2 |
|
rectifier- | inverter |
charger | |
Q1 | Q5N |
mains 1 |
|
| QF1 |
| battery |
Modular UPS with external maintenance bypass
Proceed in the following order:
◗check that all lines supplying the load are off or that the load is disconnected;
◗in the maintenance bypass cubicle, open output switch Q5N, then close bypass switch Q3BP;
◗close the upstream switch (on the
◗close the Mains 1 input switch Q1 on the UPSs to supply them with power:
Q1 | Q4S | Q5N |
OFF | ON | OFF | OFF |
(0) | (I) | (0) | (0) |
|
|
◗the rectifier/chargers automatically start;
◗red "load not protected" light 2 on the control panels of the UPSs goes on:
! | ! | + – | I | O |
2
◗close battery circuit breaker QF1 on the UPSs:
QF1
OFF | ON |
(0) | (I) |
◗close the upstream switches (on the
Q1 | Q4S | Q5N |
ON | OFF | ON | OFF |
(I) | (0) | (I) | (0) |
|
|
◗close inverter output switch Q5N on the UPSs:
Q1 | Q4S | Q5N |
ON | ON | OFF | ON |
(I) | (I) | (0) | (I) |
|
| ||
◗ close output switch Q5N in the |
| ||
maintenance bypass cubicle; |
|
| |
◗ open bypass switch Q3BP in the | |||
maintenance bypass cubicle; |
|
|
◗press the "inverter on" button 6 on the control panel of a UPS:
! | ! | + – | I | O |
| ||||
|
|
| 6 |
|
◗green "load protected" light 5 flashes for three seconds,
◗the inverter starts and waits for the start of the other units;
◗proceed in the same manner for each unit. When the number of running units is sufficient, the inverter output switches close and the load is supplied by the inverters:
◗red "load not protected" light 2 goes off,
◗green "load protected" light 5 on the control panel goes on.