APC 6739380EN/JC user manual Modular UPS with external maintenance bypass, Galaxy UPS

Page 21

Start-up (cont.)

Galaxy UPS 1

mains 2

rectifier- charger

Q1

mains 1

Q3BP

static switch

Q4S

inverter

Q5N

QF1

battery

load

Galaxy UPS 2

Q3BP

 

 

static switch

 

Q4S

mains 2

 

rectifier-

inverter

charger

Q1

Q5N

mains 1

 

 

QF1

 

battery

Modular UPS with external maintenance bypass

Proceed in the following order:

check that all lines supplying the load are off or that the load is disconnected;

in the maintenance bypass cubicle, open output switch Q5N, then close bypass switch Q3BP;

close the upstream switch (on the low-voltage switchboard) supplying power to the Mains 1 inputs on the UPSs;

close the Mains 1 input switch Q1 on the UPSs to supply them with power:

Q1

Q4S

Q5N

OFF

ON

OFF

OFF

(0)

(I)

(0)

(0)

 

 

the rectifier/chargers automatically start;

red "load not protected" light 2 on the control panels of the UPSs goes on:

!

!

+ –

I

O

2

close battery circuit breaker QF1 on the UPSs:

QF1

OFF

ON

(0)

(I)

close the upstream switches (on the low-voltage switchboard) supplying power to the Mains 2 inputs on the UPSs, then close the Mains 2 input switch Q4S on the UPSs:

Q1

Q4S

Q5N

ON

OFF

ON

OFF

(I)

(0)

(I)

(0)

 

 

close inverter output switch Q5N on the UPSs:

Q1

Q4S

Q5N

ON

ON

OFF

ON

(I)

(I)

(0)

(I)

 

 

close output switch Q5N in the

 

maintenance bypass cubicle;

 

 

open bypass switch Q3BP in the

maintenance bypass cubicle;

 

 

press the "inverter on" button 6 on the control panel of a UPS:

!

!

+ –

I

O

 

 

 

 

6

 

green "load protected" light 5 flashes for three seconds,

the inverter starts and waits for the start of the other units;

proceed in the same manner for each unit. When the number of running units is sufficient, the inverter output switches close and the load is supplied by the inverters:

red "load not protected" light 2 goes off,

green "load protected" light 5 on the control panel goes on.

6739380EN/JC - Page 21

Image 21
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System performance IntroductionSystem description System may also includeUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Frequency converters without redundancy Output voltage quality and continuityFrequency converters with redundancy Overload curveInverter cubicle Description of MGETMGalaxyTM 6000 cubicles250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleControl panel Visible control panel Static Switch CubicleVisible control panel Mgetm GalaxyTM 6000 control panelBattery operation light Buzzer Operating problem lightLoad not protected light Load protected light Hidden control panel Light G battery charging Light F battery temperature outside tolerancesLight H inverter fault Light I battery dischargedSystem start-up Start-upSingle-unit or modular UPS Multi-bypass modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a unit Parallel UPS systems with a Static Switch CubicleFrequency converters Start-up of a rectifier/chargerStart-up of an inverter Frequency converter without a batterySingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown of a unit ShutdownShutdown of an inverter Shutdown of an rectifier/chargerSystem shutdown External maintenance bypassSingle-unit or single modular Modular UPSParallel UPSs with SSC Buzzer resetNo Mains With MainsMaintenance bypass AlarmsSignal transmission Signal receptionEnvironment information Standard information Media ContactsLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Current measurements Voltage measurementsDisplay of voltage measurements Display of current measurementsBattery measurements Frequency and power measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Language, display contrast and buzzer volume settings Inverter On/Off commandsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationOptions LED signalling boxMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitHarmonics filter and power factor improvement Vision displayRemote vision display Double bridge rectifier-charger Battery Temperature MonitorEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC