APC 6739380EN/JC user manual Frequency and power measurements, Battery measurements

Page 43

"Monitor" alphanumeric display (cont.)

Frequency and power measurements

These measurements may be accessed in two manners:

Display of power and frequency measurements

pressing the "W.Hz" button displays the series of screens in the figure opposite;

in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the frequency and power measurements of a cubicle. The system shifts to the frequency and power measurements of the next cubicle.

W. Hz

FREQ. MNS1 MNS2 INV.

HZ

W. Hz

LOAD

P1

P2

P3

KW

 

 

 

 

 

Direct access to the function by pressing the "W.Hz" button.

Frequency value for Mains 1, Mains 2 and the inverter output in Hz with one decimal figure (values valid only for concerned cubicle).

Active power drawn by the load in kW on each phase.

Note:

W. Hz

Mains 2 measurements are not displayed on UPS cubicles in parallel UPS systems;

Mains 1 output measurements are not displayed on Static Switch Cubicles.

Battery measurements

P LOAD

 

 

/ Pn

 

 

 

 

 

 

=

 

 

% (PN=

 

 

 

KW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W. Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

 

 

P1

P2

 

 

P3

KVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W.Hz

P.TOTAL P.KW P.KVA LOAD

W.Hz

POWER FACTOR

LOAD P.F. =

W. Hz

Percentage of the power drawn by the load with regards to the rated unit output (in parentheses).

Apparent power drawn by the load in kVA on each phase.

Active power (in kW) and apparent power (in total kVA drawn by the load (total of the three phases)).

Load power factor (active power / apparent power).

These measurements may be accessed in two manners:

Display of battery measurements

pressing the "battery" button displays the series of screens in the figure opposite;

in "Monitor" multi-cubicle mode, pressing the ">" button when the screen already displays the battery measurements of a cubicle. The system shifts to the battery measurements of the next cubicle.

Note:

these measurements do not concern the Static Switch Cubicle. The "battery" button on the Static Switch Cubicle will display the following message for a few seconds:

COMMAND INVALID

+ –

 

 

 

UBAT. IBAT.

 

 

T° BAT.

 

 

 

 

V

*

 

 

A

 

 

 

 

 

 

°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ou

 

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE BAT.TIME

 

 

 

 

MN

%KW

 

LOAD =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REMAINING BAT.TIME

 

 

 

 

MN

%KW LOAD =

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+ –

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Direct access to the function by pressing the "battery" button.

Battery voltage, charge current (+ sign) or discharge current (- sign), battery temperature (optional).

If Mains 1 is up - available battery time in the event of a Mains 1 outage.

If Mains 1 is down or outside tolerances - remaining battery time in minutes (real time calculation).

STATIC SWITCH MODUL

the available battery time value blinks to attract attention;

the battery temperature is displayed only if the "Temperature Monitor" option is installed.

see figure on next page

Note:

Stars appear in the battery backup time display if the battery time estimator function has not been validated by the after-sales support technicians.

6739380EN/JC - Page 43

Image 43
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System may also include IntroductionSystem performance System descriptionUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Overload curve Output voltage quality and continuityFrequency converters without redundancy Frequency converters with redundancy450 to 500kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 250 to 400kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleMgetm GalaxyTM 6000 control panel Visible control panel Static Switch CubicleControl panel Visible control panelLoad protected light Buzzer Operating problem lightBattery operation light Load not protected lightHidden control panel Light I battery discharged Light F battery temperature outside tolerancesLight G battery charging Light H inverter faultMulti-bypass modular UPS Start-upSystem start-up Single-unit or modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a rectifier/charger Parallel UPS systems with a Static Switch CubicleStart-up of a unit Frequency convertersFrequency converter or multi-bypass UPS Frequency converter without a batteryStart-up of an inverter Single-unit or modular UPS systemShutdown of an rectifier/charger ShutdownShutdown of a unit Shutdown of an inverterModular UPS External maintenance bypassSystem shutdown Single-unit or single modularWith Mains Buzzer resetParallel UPSs with SSC No MainsMaintenance bypass AlarmsStandard information Media Contacts Signal receptionSignal transmission Environment informationAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Display of current measurements Voltage measurementsCurrent measurements Display of voltage measurementsDisplay of battery measurements Frequency and power measurementsBattery measurements Display of power and frequency measurementsBattery test see figure opposite Display of the settings selection screens Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display for the inverter On/Off commandsDisplay system configuration Display system configurationTele-Monitor remote indications unit LED signalling boxOptions Media Contacts 15 additional auxiliary transmissionVision display Harmonics filter and power factor improvementRemote vision display Mgetm GalaxyTM 6000UPSs standard input rectifier-charger Battery Temperature MonitorDouble bridge rectifier-charger Empty cubicles50 6739380EN/JC