"Monitor" alphanumeric display (cont.)

Display system configuration

This function may be accessed from the initial screen. Press the "*" button, followed by the "V" button in less than

Display system configuration

one second.

Note:

ensure that two "Monitor" or "Tele Monitor" units do not receive the same number;

only one master "Tele Monitor" may be installed on the display network;

this function may be accessed only with a password.

initial screen

 

*

 

V

 

 

 

 

 

 

 

 

 

PASSWORD ?

=

This function may be accessed from the initial screen. Press the "*" button, followed by the "V" button in less than one second.

Enter the password (a combination of four buttons among the control panel buttons). If the password is incorrect, the system displays the following screen for a few seconds:

INCORRECT

PASSWORD

then automatically returns to the initial screen.

DISPLAY = LOCAL >=SELECT * =CONFIRM.

DISPLAY = MASTER

>=SELECT

* =CONFIRM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

if display

 

 

 

 

if display

is master

 

 

 

 

is slave

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISPLAY NUMBER =

 

 

>=SELECT

* =CONFIRM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CUBICLE N°

 

 

 

 

= YES

>=SELECT

* =CONFIRM.

 

 

 

 

initial screen

 

 

 

 

 

 

 

 

 

 

DISPLAY N°

 

 

 

 

= YES

>=SELECT

*=CONFIRM.

 

 

 

 

 

 

 

 

 

 

CUBICLE N°

 

 

= YES

>=SELECT

*=CONFIRM.

 

 

 

 

 

GIANT DISPLAY =YES >=SELECT *=CONFIRM.

Selection of the type of display: local ("Monitor") or distant ("Tele Monitor"). If the display is distant, the local buzzer is deactivated.

Selection of display role on the network: master (only one display may be the master) or slave.

Selection of the slave display number (multi- display installation) from 1 to 10.

Selection of the numbers of the cubicles that the display must control. Ten cubicle numbers are successively presented. Select "yes" if the display is to control the cubicle or "no" if it does not control the cubicle or if the cubicle does not exist. Confirm using the "*" button. The system goes on to the next cubicle number. Following confirmation of the last cubicle number, the system automatically returns to the initial screen.

Selection of the numbers of the slave displays controlled by the master display. Ten display number are successively presented. Select "yes" if the master display is to control the slave display or "no" if it does not control the display or if the display does not exist. Confirm using the "*" button. The system goes on to the next display.

Selection of the numbers of the cubicles controlled by the display. Eight cubicle number are successively presented. Select "yes" if the display is to control the cubicle or "no" if it does not control the cubicle or if the cubicle does not exist. Confirm using the "*" button. The system goes on the next screen.

Confirmation as to whether the installation is equipped with a giant screen. Following confirmation using the "*" button, the system automatically returns to the initial screen.

initial screen

Page 46 - 6739380EN/JC

Image 46
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System description IntroductionSystem performance System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Frequency converters with redundancy Output voltage quality and continuityFrequency converters without redundancy Overload curve250 to 400kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 450 to 500kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Visible control panel Static Switch CubicleControl panel Mgetm GalaxyTM 6000 control panelLoad not protected light Buzzer Operating problem lightBattery operation light Load protected lightHidden control panel Light H inverter fault Light F battery temperature outside tolerancesLight G battery charging Light I battery dischargedSingle-unit or modular UPS Start-upSystem start-up Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSFrequency converters Parallel UPS systems with a Static Switch CubicleStart-up of a unit Start-up of a rectifier/chargerSingle-unit or modular UPS system Frequency converter without a batteryStart-up of an inverter Frequency converter or multi-bypass UPSShutdown of an inverter ShutdownShutdown of a unit Shutdown of an rectifier/chargerSingle-unit or single modular External maintenance bypassSystem shutdown Modular UPSNo Mains Buzzer resetParallel UPSs with SSC With MainsAlarms Maintenance bypassEnvironment information Signal receptionSignal transmission Standard information Media ContactsAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Display of voltage measurements Voltage measurementsCurrent measurements Display of current measurementsDisplay of power and frequency measurements Frequency and power measurementsBattery measurements Display of battery measurementsBattery test see figure opposite Display for the inverter On/Off commands Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display of the settings selection screensDisplay system configuration Display system configurationMedia Contacts 15 additional auxiliary transmission LED signalling boxOptions Tele-Monitor remote indications unitVision display Harmonics filter and power factor improvementRemote vision display Empty cubicles Battery Temperature MonitorDouble bridge rectifier-charger Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC