APC 6739380EN/JC System shutdown, Single-unit or single modular, External maintenance bypass

Page 25

System shutdown

Single-unit or single modular

UPS

shutdown the inverter (see the "shutdown of a module" section);

carry out operations in the following order:

close maintenance bypass switch Q3BP:

open Mains 2 input switch Q4S:

Q1 Q4S Q3BP Q5N

ON

ON

OFF

ON

OFF

 

 

(I)

(I)

(0)

(I)

(0)

 

 

 

Shutdown (cont.)

open Mains 1 input switch Q1:

Q1 Q4S Q3BP Q5N

ON OFF

OFF

ON

OFF

(I)

(0)

(0)

(I)

(0)

 

 

 

Q1 Q4S Q3BP Q5N

ON

ON

OFF

ON

ON

(I)

(I)

(0)

(I)

(I)

 

 

 

open output switch Q5N:

Q1 Q4S Q3BP Q5N

ON

ON

ON

ON OFF

 

 

(I)

(I)

(I)

(I)

(0)

 

 

 

open battery circuit breaker QF1:

QF1

ON OFF

(I)

(0)

the UPS is powered down (except the Mains cables upstream from switches Q1, Q4S and Q3BP) and the load is supplied by Mains 2. All the lights on the control panel are off. A full powering down requires load shutdown and the opening of the upstream protection devices on Mains 1 and 2.

Modular UPS with external maintenance bypass

shutdown each UPS (see section "shutdown of a unit");

transfer to the maintenance bypass in the order indicated below (the load is supplied directly by Mains 2 via bypass switch Q3BP):

in the maintenance bypass cubicle, close switch Q3BP, then open switch Q5N;

open output switch Q5N for each UPS;

cut the Mains 2 supply to each UPS by opening the upstream protection devices;

open battery circuit breaker QF1 on each UPS;

open input switch Q1 on each UPS;

the UPSs are de-energised once the capacitors have discharged.

External maintenance bypass

 

Q3BP

Modular UPS 1

 

Q4S

static switch

 

mains 2

 

rectifier-

inverter

charger

Q1

Q5N

mains 1

 

QF1

 

 

battery

Modular UPS 2

load

 

 

Q5N

Q4S

static switch

 

mains 2

 

rectifier-

inverter

charger

Q1

Q5N

mains 1

 

QF1

 

 

battery

 

6739380EN/JC - Page 25

Image 25
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System performance IntroductionSystem description System may also includeUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Frequency converters without redundancy Output voltage quality and continuityFrequency converters with redundancy Overload curveInverter cubicle Description of MGETMGalaxyTM 6000 cubicles250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleControl panel Visible control panel Static Switch CubicleVisible control panel Mgetm GalaxyTM 6000 control panelBattery operation light Buzzer Operating problem lightLoad not protected light Load protected lightHidden control panel Light G battery charging Light F battery temperature outside tolerancesLight H inverter fault Light I battery dischargedSystem start-up Start-upSingle-unit or modular UPS Multi-bypass modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a unit Parallel UPS systems with a Static Switch CubicleFrequency converters Start-up of a rectifier/chargerStart-up of an inverter Frequency converter without a batterySingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown of a unit ShutdownShutdown of an inverter Shutdown of an rectifier/chargerSystem shutdown External maintenance bypassSingle-unit or single modular Modular UPSParallel UPSs with SSC Buzzer resetNo Mains With MainsMaintenance bypass AlarmsSignal transmission Signal receptionEnvironment information Standard information Media ContactsAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Current measurements Voltage measurementsDisplay of voltage measurements Display of current measurementsBattery measurements Frequency and power measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Language, display contrast and buzzer volume settings Inverter On/Off commandsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationOptions LED signalling boxMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitVision display Harmonics filter and power factor improvementRemote vision display Double bridge rectifier-charger Battery Temperature MonitorEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC