Environment information

Standard information Media Contacts 9

Terminals XR1, XR2, XR3 and XR4 on the remote transmission board of each type of unit can be used for the input of data from the operating environment and for the transmission of signals on the operational status of the device (see figures 18, 19, 20 and 22 for the position of the board).

Remote transmission board

XR1 XR2 XR3 XR4

Signal reception

The signals should be provided by volt- free contacts.

emergency shutdown. An NC contact causes:

rapid shutdown of the inverter and the RC,

opening of battery circuit breaker QF1,

transfer of the load to Mains 2 (generally without interruption in the supply of power);

battery room ventilation fault:

a NO contact causes the shutdown of the RC;

battery circuit breaker QF1 closed: a NO contact inhibits inverter start-up when the breaker is open;

battery temperature: an optional PC-board may be connected to the remote transmission board. It supplies information on the battery temperature, thus enabling the RC to regulate the battery voltage.

Note:

The Static Switch Cubicle does not receive any of the above signals.

Signal transmission

an auxiliary 24V power supply, isolated and backed up, is used to supply:

the undervoltage coil release for the battery circuit breaker(s) QF1,

an optional board that measures the temperature in the battery room;

"general alarm" information

(2 volt-free changeover contacts) which includes:

internal faults,

information on temperatures outside tolerances in the battery room (optional),

overload information (I > In),

static switch ventilation and power- supply faults;

"low battery shutdown" warning signal (2 volt-free changeover contacts) indicating that battery time is about to run out. The warning threshold may be personalized;

"load on inverter" signal (2 volt- free changeover contacts) indicating that the load is supplied by the inverter. In single-unit UPS systems, one volt- free changeover contact may be used to indicate that the load is supplied by Mains 2;

"load on battery" signal (2 volt-free changeover contacts) indicating that the inverter is supplied by the battery in the following cases:

Mains 1 outage or voltage drop,

RC shutdown,

RC current limiting;

This signal, which may be used to initiate process saving and shutdown procedures, is time-delayed by 30 seconds to avoid unnecessary operations following micro-breaks;

"maintenance position" signal (2 volt-free changeover contacts) indicating that;

maintenance bypass switch Q3BP is closed,

Mains 2 input switch Q4S is open,

inverter output switch Q5N is open,

battery circuit breaker QF1 is open;

signal to open battery circuit breaker(s) QF1 in the event the "emergency shutdown" button being pressed or to avoid an excessive battery discharge (more than 3 rated time).

Note:

the maximum breaking capacity of

the changeover contacts is 5A at 250V;

information on the battery is not supplied to frequency converters without a battery or to the Static Switch Cubicle;

in systems with a Static Switch Cubicle, the "load on inverter" and "maintenance position" signals must be directed to the Static Switch Cubicle.

Page 28 - 6739380EN/JC

Image 28
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options Introduction System performanceSystem description System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Isolation and protection devices Static Switch CubicleUPS or converter cubicles Normal operation Main operating modesOperation with Mains 1 down Operation with Mains 1 restored Battery timeBattery charge cycle Example of an installation with an engine generator set Installation with an engine generator setUPS shutdown or overload Output voltage quality and continuity Frequency converters without redundancyFrequency converters with redundancy Overload curveDescription of MGETMGalaxyTM 6000 cubicles Inverter cubicle250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterKVA UPS Battery cubicleFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Static Switch Cubicle Control panelVisible control panel Mgetm GalaxyTM 6000 control panelBuzzer Operating problem light Battery operation lightLoad not protected light Load protected lightHidden control panel Light F battery temperature outside tolerances Light G battery chargingLight H inverter fault Light I battery dischargedStart-up System start-upSingle-unit or modular UPS Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSParallel UPS systems with a Static Switch Cubicle Start-up of a unitFrequency converters Start-up of a rectifier/chargerFrequency converter without a battery Start-up of an inverterSingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown Shutdown of a unitShutdown of an inverter Shutdown of an rectifier/chargerExternal maintenance bypass System shutdownSingle-unit or single modular Modular UPSBuzzer reset Parallel UPSs with SSCNo Mains With MainsAlarms Maintenance bypassSignal reception Signal transmissionEnvironment information Standard information Media ContactsAdditional information Media Contacts 15 optional LED signalling box optionalAdditional remote transmission board 30 6739380EN/JC Maintenance configuration MaintenanceSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesVisual check AutodiagnosticsFunctional check Training centers General Monitor alphanumeric displayDisplay Green lights Lights 1 toRed lights List of general alarms Alarm display and buzzer resetDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Voltage measurements Current measurementsDisplay of voltage measurements Display of current measurementsFrequency and power measurements Battery measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Inverter On/Off commands Language, display contrast and buzzer volume settingsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationLED signalling box OptionsMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitVision display Harmonics filter and power factor improvementRemote vision display Battery Temperature Monitor Double bridge rectifier-chargerEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC