APC 6739380EN/JC user manual Shutdown of a unit, Shutdown of an inverter

Page 24

Shutdown

Shutdown of a unit

Shutdown of an inverter

press the "inverter off" button 7 on the control panel for 3 seconds;

!

!

+ –

I

O

 

 

 

 

7

 

Single-unit UPS

green "load protected" light 5 goes off,

red "load not protected" light 2 on the control panel goes on,

the inverter stops;

if transfer to Mains 2 conditions are correct, the inverter shuts down and the load is transferred to Mains 2;

if transfer to Mains 2 conditions are not correct, the inverter does not shut down;

special action on the hidden control panel is required to force inverter shutdown,

to force inverter shutdown, press

simultaneously the security button 14 and button 5 "Forced inverter shutdown" 17 on the hidden control panel,

the load is transferred to Mains 2 with a 0.8 second interruption in the supply of power.

Multi-bypass modular UPS:

the UPS shuts down (the other parallel-connected unit can supply the entire load):

green "load protected" light 5 goes off,

Modular UPS with external maintenance bypass:

all the UPSs shut down:

green "load protected" light 5 goes off,

red "load not protected" light 2 on the control panel of each unit goes on,

orange "operating problem" light 3 on the other units goes on, all shut down due to the overload.

Frequency converter:

if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts down:

green "load protected" light 5 goes off,

red "load not protected" light 2 lights on the control panel of the line; The load is not affected in that the other inverters continue to supply it normally;

if the system is not redundant, all the inverters shut down;

green "load protected" light 5 goes off,

red "load not protected" light 2 on the control panel of each line goes on,

orange "operating problem" light 3 on the control panel of the other lines goes on, all shut down due to the overload.

Parallel UPS with SSC:

if the system is redundant, i.e. the other parallel-connected inverters can supply the load on their own, the inverter shuts down:

green "load protected" light 5 goes off,

red "load not protected" light 2 lights on the control panel of the line. The load is not affected in that the other inverters continue to supply it normally;

if the system is not redundant and the transfer to Mains 2 conditions are correct, all the inverters shut down;

green "load protected" light 5

goes off,

red "load not protected" light 2 lights on the control panel of each line,

orange "operating problem" light 3 on the control panel of the other lines goes on (all shut down due to the overload),

the load is transferred to Mains 2 without an interruption in the supply of power;

if the system is not redundant and the transfer to Mains 2 conditions are not correct, the inverter does not shut down;

special action on the hidden control panel is required to force inverter shutdown,

to force inverter shutdown, press

simultaneously the security button 14 and button 5 "Forced inverter shutdown" 17 on the hidden control panel,

the load is transferred to Mains 2 with a 0.8 second interruption in the supply of power.

red "load not protected" light 2 on the control panel goes on.

The load is not affected and continues to be supplied by the other unit.

Shutdown of an rectifier/charger

Except in frequency converters without a battery, it is recommended not to stop the rectifier/charger because the battery will no longer be charged. Except in the case of a test of the inverter on battery power, the rectifier/ charger should be shutdown after the inverter to avoid unnecessary battery discharge.

Proceed in the following order:

open battery circuit breaker QF1;

open Mains 1 input switch Q1;

the rectifier/charger shuts down,

all control panel lights go off because the device is powered down.

Note:

In a frequency converter without a battery, rectifier/charger shutdown automatically results in inverter shutdown.

Page 24 - 6739380EN/JC

Image 24
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options Introduction System performanceSystem description System may also includeDifferent types of MGETMGalaxyTM 6000 systems Up to 4 UPS identical ratings can be parallel-connectedFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Output voltage quality and continuity Frequency converters without redundancyFrequency converters with redundancy Overload curveDescription of MGETMGalaxyTM 6000 cubicles Inverter cubicle250 to 400kVA UPS or frequency converter 450 to 500kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS Static Switch Cubicle External maintenance bypass cubicleVisible control panel Static Switch Cubicle Control panelVisible control panel Mgetm GalaxyTM 6000 control panelBuzzer Operating problem light Battery operation lightLoad not protected light Load protected lightHidden control panel Light F battery temperature outside tolerances Light G battery chargingLight H inverter fault Light I battery dischargedStart-up System start-upSingle-unit or modular UPS Multi-bypass modular UPSModular UPS with external maintenance bypass Galaxy UPSParallel UPS systems with a Static Switch Cubicle Start-up of a unitFrequency converters Start-up of a rectifier/chargerFrequency converter without a battery Start-up of an inverterSingle-unit or modular UPS system Frequency converter or multi-bypass UPSShutdown Shutdown of a unitShutdown of an inverter Shutdown of an rectifier/chargerExternal maintenance bypass System shutdownSingle-unit or single modular Modular UPSBuzzer reset Parallel UPSs with SSCNo Mains With MainsAlarms Maintenance bypassSignal reception Signal transmissionEnvironment information Standard information Media ContactsLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Frequency converter or parallel UPS with SSC Isolate the UPSsBattery maintenance Vented lead-acid batteriesAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms List of secondary alarms Mains 2 Problem Check FrequencyBattery is currently being recharged Measurement system Voltage measurements Current measurementsDisplay of voltage measurements Display of current measurementsFrequency and power measurements Battery measurementsDisplay of power and frequency measurements Display of battery measurementsBattery test see figure opposite Inverter On/Off commands Language, display contrast and buzzer volume settingsDisplay for the inverter On/Off commands Display of the settings selection screensDisplay system configuration Display system configurationLED signalling box OptionsMedia Contacts 15 additional auxiliary transmission Tele-Monitor remote indications unitHarmonics filter and power factor improvement Vision displayRemote vision display Battery Temperature Monitor Double bridge rectifier-chargerEmpty cubicles Mgetm GalaxyTM 6000UPSs standard input rectifier-charger50 6739380EN/JC