APC 6739380EN/JC user manual List of secondary alarms, Mains 2 Problem Check Frequency

Page 39

"Monitor" alphanumeric display (cont.)

List of secondary alarms

These alarm messages may be consulted by pressing the "alarms" ("!") button when the "!" character appears at the end of a general alarm message. The "alarms" ("!") button can then be used to read the other alarms from the list.

EMERGENCY SHUTDOWN

AUXILIARY COMMAND !

The remote emergency-shutdown button has been pressed with as a result:

shutdown of the inverter;

shutdown of the rectifier/charger;

opening of battery circuit breaker QF1;

transfer of the load to Mains 2. To ensure full powering down of the system, this button must also open the external upstream circuit breakers supplying Mains 1 and 2.

LOAD ON

MAINS 2

!

The load has been transferred to Mains 2 and is no longer protected.

MAINS 2 PROBLEM

CHECK FREQUENCY !

Mains 2 frequency is outside tolerances and the inverter, unable to synchronize, has switched to free-running frequency mode. Transfer of the load from the inverter to Mains 2 or vice-versa will result in an interruption of the supply of power to the load.

MAINS 2 PROBLEM

CHECK VOLTAGE

!

Mains 2 voltage is outside tolerances. Transfer of the load from the inverter to Mains 2 or vice-versa will result in an interruption of the supply of power to the load.

FREQUENCY IMPOSED

DESYNCH. COMMAND !

The inverter has received an external command to desynchronize its output frequency with that of Mains 2.

INVERTER IMPOSED

AUXILIARY COMMAND !

The inverter has received an auxiliary command inhibiting transfer to Mains 2. In the event of an inverter malfunction and shutdown, the load will no longer be supplied.

BATTERY OVERTEMP.

CHECK FANS

!

This message is displayed only if the "Temperature Monitor" option has been installed. It signals that the battery temperature is outside tolerances.

BATT. HOUSING VENT

OR HARM FILTER FAULT!

A fault requiring servicing has occurred in the battery room ventilation system. The rectifier-charger stops after

30 seconds.

If the installation includes a harmonics filter, this light will also signal an overtemperature of the filter’s inductor.

MAINS 1 PROBLEM

CHECK FREQUENCY !

Mains 1 frequency is outside tolerances and the RC has shut down. The inverter is on battery power.

MAINS 1 PROBLEM

CHECK VOLTAGE

!

Mains 1 is down or its voltage is outside tolerances and the rectifier/charger has shut down. The inverter is on battery power.

CHARGER SHUTDOWN

AUXILIARY COMMAND !

The rectifier/charger has received an external command to progressively shut down (for example, for a progressive transfer to an engine generator set).

INPUT KVA LIMITED

AUXILIARY COMMAND !

The rectifier/charger has received an external command to limit the power drawn on Mains 1. The remaining power required for the load is supplied by the battery. This situation is encountered, for example, when the system operates on power supplied by

an undersized engine generator set.

I BATTERY LIMITED

AUXILIARY COMMAND !

The rectifier/charger has received an external command to limit the charge current supplied to the battery. The normal charge current will be supplied when Mains 1 returns. This situation is encountered, for example, when the system operates on power supplied by an undersized engine generator set.

Note:

The battery charge current limit value may be programmed.

BATTERY BREAKER

QF1 OPEN

!

QF1 battery circuit breaker has tripped or is open. The load is no longer protected because battery power in unavailable in the event of a Mains 1 outage.

LOW BATTERY

...!

The inverter has shut down at the end of battery power.

CHARGER OFF

...!

The rectifier/charger has shut down.

CHARGER FAULT

CALL SUPPORT DEPT.!

A fault has occurred in the rectifier/ charger module requiring servicing by the after-sales support department.

MAINS 1 SWITCH

Q1 OPEN

!

Mains 1 input switch Q1 is open. It must be closed for rectifier/charger start-up.

I INVERTER > IN

CHECK P.F. KW

An inverter overload has occurred due to a load power factor greater than 0.9. The blinking "kW" sign at the end of the message is a prompt to read the load power factor.

6739380EN/JC - Page 39

Image 39
Contents Mgetm GalaxyTM 2 6739380EN/JC Contents Options System may also include IntroductionSystem performance System descriptionUp to 4 UPS identical ratings can be parallel-connected Different types of MGETMGalaxyTM 6000 systemsFrequency converter with battery backup power figure Static Switch Cubicle Isolation and protection devicesUPS or converter cubicles Main operating modes Normal operationOperation with Mains 1 down Battery time Operation with Mains 1 restoredBattery charge cycle Installation with an engine generator set Example of an installation with an engine generator setUPS shutdown or overload Overload curve Output voltage quality and continuityFrequency converters without redundancy Frequency converters with redundancy450 to 500kVA UPS or frequency converter Description of MGETMGalaxyTM 6000 cubiclesInverter cubicle 250 to 400kVA UPS or frequency converterBattery cubicle KVA UPSFor a 250 to 300kVA UPS External maintenance bypass cubicle Static Switch CubicleMgetm GalaxyTM 6000 control panel Visible control panel Static Switch CubicleControl panel Visible control panelLoad protected light Buzzer Operating problem lightBattery operation light Load not protected lightHidden control panel Light I battery discharged Light F battery temperature outside tolerancesLight G battery charging Light H inverter faultMulti-bypass modular UPS Start-upSystem start-up Single-unit or modular UPSGalaxy UPS Modular UPS with external maintenance bypassStart-up of a rectifier/charger Parallel UPS systems with a Static Switch CubicleStart-up of a unit Frequency convertersFrequency converter or multi-bypass UPS Frequency converter without a batteryStart-up of an inverter Single-unit or modular UPS systemShutdown of an rectifier/charger ShutdownShutdown of a unit Shutdown of an inverterModular UPS External maintenance bypassSystem shutdown Single-unit or single modularWith Mains Buzzer resetParallel UPSs with SSC No MainsMaintenance bypass AlarmsStandard information Media Contacts Signal receptionSignal transmission Environment informationLED signalling box optional Additional information Media Contacts 15 optionalAdditional remote transmission board 30 6739380EN/JC Maintenance Maintenance configurationSingle-unit or single modular UPS figure Isolate the UPSs Frequency converter or parallel UPS with SSCVented lead-acid batteries Battery maintenanceAutodiagnostics Visual checkFunctional check Training centers Monitor alphanumeric display GeneralDisplay Lights 1 to Green lightsRed lights Alarm display and buzzer reset List of general alarmsDisplay of alarms Mains 2 Problem Check Frequency List of secondary alarmsBattery is currently being recharged Measurement system Display of current measurements Voltage measurementsCurrent measurements Display of voltage measurementsDisplay of battery measurements Frequency and power measurementsBattery measurements Display of power and frequency measurementsBattery test see figure opposite Display of the settings selection screens Inverter On/Off commandsLanguage, display contrast and buzzer volume settings Display for the inverter On/Off commandsDisplay system configuration Display system configurationTele-Monitor remote indications unit LED signalling boxOptions Media Contacts 15 additional auxiliary transmissionHarmonics filter and power factor improvement Vision displayRemote vision display Mgetm GalaxyTM 6000UPSs standard input rectifier-charger Battery Temperature MonitorDouble bridge rectifier-charger Empty cubicles50 6739380EN/JC