Table 11.4 Recommended Cable Size and Tightening Torque for 180kVA UPS.
Block Number | Cable Size | Tightening Torque |
|
|
|
1 | Two 2/0 or larger | 5.8 |
|
|
|
2 | Two 2/0 or larger | 5.8 |
|
|
|
3 | Two 2/0 or larger | 5.8 |
|
|
|
4 | Two 2/0 or larger | 5.8 |
|
|
|
5 | Two 2/0 or larger | 5.8 |
|
|
|
6 | Two 2/0 or larger | 5.8 |
|
|
|
7 | Two 2/0 or larger | 5.8 |
|
|
|
8 | Two 2/0 or larger | 5.8 |
|
|
|
9 | Two 2/0 or larger | 5.8 |
|
|
|
10 | Two 2/0 or larger | 5.8 |
|
|
|
11 | Two 2/0 or larger | 5.8 |
|
|
|
*12 | Two 4/0 or larger | 5.8 |
|
|
|
*13 | Two 4/0 or larger | 5.8 |
|
|
|
NOTE: Maximum cable size is 350MCM.
*Two battery strings or more (consult factory if using one battery string).
Table 11.5 Recommended Cable Size and Tightening Torque for 225kVA UPS.
| Block Number | Cable Size | Tightening Torque |
|
|
|
|
| 1 | Two 2/0 or larger | 5.8 |
|
|
|
|
| 2 | Two 2/0 or larger | 5.8 |
| 3 | Two 2/0 or larger | 5.8 |
| 4 | Two 2/0 or larger | 5.8 |
| 5 | Two 2/0 or larger | 5.8 |
| 6 | Two 2/0 or larger | 5.8 |
| 7 | Two 2/0 or larger | 5.8 |
| 8 | Two 2/0 or larger | 5.8 |
| 9 | Two 2/0 or larger | 5.8 |
| 10 | Two 2/0 or larger | 5.8 |
| 11 | Two 2/0 or larger | 5.8 |
| *12 | Two 4/0 or larger | 5.8 |
|
|
|
|
| *13 | Two 4/0 or larger | 5.8 |
|
|
|
|
NOTE: Maximum cable size is 350MCM.
*Two battery strings or more (consult factory if using one battery string).