Toshiba G8000 Series installation manual Grounding configuration with corner-grounded delta-input

Page 40

11.6.4Grounding configuration with corner-grounded delta-input

If a phase of delta-input source is grounded (B-phase for example), the ground bus in the UPS cabinet should NOT be connected to the neutral terminal of UPS output. So, the jumper cable should be disconnected. See Figure 11.9 for the jumper cable location.

The UPS output is floating against ground during normal operation. An isolation transformer is recommended at output distribution as shown in Figure 11.12.

Input Source

3

B

3

G

 

< UPS Cabinet >

3

 

N

 

3

3

 

 

N

G

G

Output Distribution

3

3

N

To the

Load

G

Disconnect

The Cable

Figure 11.12 - Grounding configuration with corner-grounded delta-input.

39

Image 40
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Do not install the UPS close to a water source Keep the UPS room cleanKeep the specified clearance around the UPS Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Transportation Avoid vibration or shock exceeding 0.5 G to the UPSDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundPoints to be observed UnpackingUPS Clearance Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input
Related manuals
Manual 63 pages 16.31 Kb