Toshiba G8000 Series Terminal Blocks and Power Cables, Phase 3-wire Phase 4-wire

Page 29

11.2 Terminal Blocks and Power Cables

The terminal blocks are shown in Figure 11.2 and are located inside at the bottom of each

100/125/150/180/225kVA UPS.

External cable size and tightening torque are recommended in the Table 11.1~11.5. Only copper wires

are allowed for external cables.

1

2

3

4

5

6

 

7

8

9

10

 

11

 

12

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U V W

U V W

N

U V W

N

-

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC INPUT

 

BYPASS INPUT

 

 

 

AC OUTPUT

 

 

BATTERY

3-Phase 3-wire

 

3-Phase 4-wire

 

 

 

3-Phase 4-wire

 

 

 

 

 

 

Figure 11.2 - Terminal Blocks of 100/125/150/180/225kVA UPS.

Table 11.1 Recommended Cable Size and Tightening Torque for 100kVA UPS.

 

Block Number

Cable Size

Tightening Torque

 

 

 

 

 

1

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

2

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

3

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

4

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

5

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

6

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

7

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

8

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

9

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

10

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

11

AWG 1/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

*12

AWG 3/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

 

*13

AWG 3/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

 

NOTE: Maximum cable size is 350MCM.

*One battery string (consult factory if using multiple battery strings).

28

Image 29
Contents Document Number February Introduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeGeneral Safety Instructions Important Safety Instructions Safety Precautions Prohibited General Terms Do not remove the rear/side panelsAvoid vibration or shock exceeding 0.5G to the UPS Installation PrecautionsUPS Installation Environment Standard Keep the specified clearance around the UPS Keep the UPS room cleanDo not install the UPS close to a water source Mandatory Connect ground wire to the earth ground terminal onlyLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents 100/125kVA UPS Exterior dimensions front & right side Dimensions and Weight150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Avoid vibration or shock exceeding 0.5 G to the UPS TransportationDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Ensure that there is adequate working space around InstallationUPS Clearance UnpackingPoints to be observed Anchor bolt tightening Anchor boltsOverview External Wiring DiagramPhase 3-wire Phase 4-wire Terminal Blocks and Power CablesRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breaker Rating External Breakers100~225kVA 250/300kVA Grounding Wire10 External Connections Control WiresRecommended configuration with input neutral grounded Grounding configurationRecommended configuration with delta-input Grounding configuration without input neutral12 Grounding configuration with corner-grounded delta-input Grounding configuration with corner-grounded delta-input