Toshiba G8000 Series installation manual Phase 3-wire Phase 4-wire

Page 32

Three cable knockout plates are provided at bottom of each 100/125/150/180/225kVA UPS. Holes are recommended in Figure 11.3.

The installing electrical contractor must punch the 5 holes.

0.8”

Plate #1

Plate #2

Plate #3

4” Dia.

2” Dia.

0.4”

AC Input

Bypass

AC Output

Battery

Control

 

 

 

 

Wires

Three solid rectangles show the cable knockout plates’ outline. The dashed rectangle shows the UPS opening under the plates.

Figure 11.3 - Cable knockout plates at the bottom (100~225kVA).

The terminal busses are shown in Figure 11.4. The busses are located inside of the 250/300kVA UPS at the top. The dashed line shows the side view of the screw holes. The screws are used to tighten the lugs.

External cable size recommendations are located in Table 11.6 and 11.7. These tables show only the torque to tighten a terminal bus & a corresponding lug. Torque to tighten the cable end in a compression lug shall be specified by the lug vendor recommended in Table 11.8.

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

 

10

 

11

 

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

U V W

-

+

 

U V W

N

U V W

 

 

 

 

 

 

 

AC INPUT

BATTERY

BYPASS INPUT

 

AC OUTPUT

3-phase 3-wire

 

 

 

3-phase 4-wire

 

3-phase 4-wire

Figure 11.4 - Terminal Busses of the 250/300kVA UPS.

31

Image 32
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Keep the specified clearance around the UPS Keep the UPS room cleanDo not install the UPS close to a water source Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Transportation Avoid vibration or shock exceeding 0.5 G to the UPSDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundUPS Clearance UnpackingPoints to be observed Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input