Toshiba G8000 Series installation manual Grounding configuration without input neutral

Page 39

11.6.2 Grounding configuration without input neutral

When the neutral line cannot be fed to the bypass input from the input source which is wye-connected, the neutral terminal in the UPS cabinet must be connected to the ground bus in order to stabilize the UPS potential as shown in Figure 11.10. Thus, the jumper cable should stay on. See Figure 11.9 for the jumper cable location.

However, there will be circulating current between the UPS and the bypass, whenever the UPS transfers to/from the bypass. And the current will flow through the ground path instead of neutral line like that in Figure 11.8.

Input Source

3

N

3

G

 

< UPS Cabinet >

3

 

N

 

3

3

 

 

N

G

G

3

 

 

 

 

N

To the

 

 

 

 

G

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep the

Cable on

Figure 11.10 - Grounding configuration without input neutral.

If a ground fault interrupter is installed, the system is likely to trip the interrupter during transferring to/from the bypass circuit. It is recommended to put 0.5 sec or longer delay on the ground fault interrupter.

11.6.3Recommended configuration with delta-input

If the input source has a delta-connection (3-phase 3-wire) without ground, the neutral terminal in the UPS cabinet must be connected to the ground bus as shown in Figure 11.11.

So, the jumper cable should stay on. See Figure 11.9 for the jumper cable location.

Input Source

3

3

G

 

< UPS Cabinet >

3

 

N

 

3

3

 

 

N

G

G

3

 

 

 

 

 

N

 

 

To the

 

 

 

 

 

G

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keep the

Cable on

Figure 11.11 - Grounding configuration with non-grounded delta-input.

38

Image 39
Contents Document Number February Introduction Uninterruptible Power Supply Contacting Toshiba’s Customer Support Center Manual’s Purpose and ScopeGeneral Safety Instructions Important Safety Instructions Safety Precautions Prohibited General Terms Do not remove the rear/side panelsAvoid vibration or shock exceeding 0.5G to the UPS Installation PrecautionsUPS Installation Environment Standard Keep the UPS room clean Do not install the UPS close to a water sourceKeep the specified clearance around the UPS Mandatory Connect ground wire to the earth ground terminal onlyLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents 100/125kVA UPS Exterior dimensions front & right side Dimensions and Weight150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Transportation by a crane TransportationAvoid vibration or shock exceeding 0.5 G to the UPS Do not expose the UPS to waterAngle more than Transportation by a forklift Storage Ensure that there is adequate working space around InstallationUnpacking Points to be observedUPS Clearance Anchor bolt tightening Anchor boltsOverview External Wiring DiagramPhase 3-wire Phase 4-wire Terminal Blocks and Power CablesRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breaker Rating External Breakers100~225kVA 250/300kVA Grounding Wire10 External Connections Control WiresRecommended configuration with input neutral grounded Grounding configurationRecommended configuration with delta-input Grounding configuration without input neutral12 Grounding configuration with corner-grounded delta-input Grounding configuration with corner-grounded delta-input
Related manuals
Manual 63 pages 16.31 Kb