Toshiba G8000 Series installation manual Grounding configuration

Page 38

11.6 Grounding configuration

This section describes the grounding configuration with AC input service entrance.

As inadequate grounding configuration causes problems on start-up, connections for the ground line and the neutral line must be done properly according to the system configuration.

11.6.1 Recommended configuration with input neutral grounded

Figure 11.8 shows recommended grounding configuration with input neutral grounded.

The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should be open, as the neutral line must be grounded only at one point in a system. And the neutral line must be properly fed to the bypass input.

Input Source

3

N

3

G

 

< UPS Cabinet >

3

 

N

 

3

3

 

 

N

G

G

3

 

 

 

 

 

N

 

 

To the

 

 

 

 

 

G

 

 

Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Disconnect

The Cable

Figure 11.8 - Grounding configuration with input neutral grounded.

A jumper cable of 2AWG (or 38mm2) is provided between the neutral terminal and ground bus in the UPS cabinet. Notice that the electrical contractor should unscrew and disconnect the jumper cable in this configuration. The cable location is illustrated below.

 

< 100~225kVA >

 

Ground

Neutral

 

Terminal

 

Bus

 

Disconnect

 

 

 

 

 

 

 

 

Jumper

 

 

 

Cable here

< 250/300kVA >

Neutral

Terminal

Ground

Bus

Disconnect

Jumper

Cable here

Figure 11.9 - Jumper cable between the neutral terminal & ground bus.

37

Image 38
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Keep the specified clearance around the UPS Keep the UPS room cleanDo not install the UPS close to a water source Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Do not expose the UPS to water TransportationAvoid vibration or shock exceeding 0.5 G to the UPS Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundUPS Clearance UnpackingPoints to be observed Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input