11.4 Grounding Wire

Be sure to ground the UPS as specified.

WARNING

Using the UPS without a proper ground will deteriorate the

insulation and may cause electric shock due to leakage currents.

 

 

The resistance to ground should be 10Ω or less.

A grounding bus is provided on the inside of the each unit. The bus is located on the front at the bottom of the UPS units. For the 250/300kVA unit, it is located on the top left. See chapter 7 “Dimensions and Weight” for bus location detailed.

It is recommended that 2 AWG (or 38mm2) or larger cable be used for the grounding wire. The wire shall be fed through an opening at the bottom, or through a hole on a knockout plate (250/300kVA only). See Figure 11.5 for knockout plate detail. Only one of 2 ground buses on top and at bottom shall be connected to the ground for 250/300kVA.

The cable end must have Amp terminal of 1/2” (12mm) diameter hole to tighten with ground bus inside the UPS, as the ground bus has 33/64” (13mm) screw hole.

The Amp terminal and ground bus shall be tightened with a 7/16” (10mm) diameter screw.

< 100~225kVA >

 

< 250/300kVA >

 

 

Through knockout plate

 

 

On top (Recommended)

 

 

10mm

 

 

OR

 

 

7/16”

 

 

Screw

Ground bus

10mm or 7/16”

 

Screw

 

 

12mm or 1/2”

 

 

Terminal

 

2AWG (38mm2)

Feed

Another way

 

Through

For grounding

 

Opening

 

 

To the facility Earth ground

Note:

Only one top or bottom should be connected to ground.

Figure 11.6 - Earth Ground Wiring.

35

Image 36
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Keep the UPS room clean Do not install the UPS close to a water sourceKeep the specified clearance around the UPS Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Transportation Avoid vibration or shock exceeding 0.5 G to the UPSDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundUnpacking Points to be observedUPS Clearance Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input