Table 11.6 Recommended Cable Size and Tightening Torque for 250kVA UPS.
| Bus Number | Cable Size | Torque to tighten |
| the terminal bus | ||
|
|
| |
|
|
|
|
| 1 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 2 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 3 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| *4 | Two 350MCM or larger | 2.5~4.5 |
|
|
|
|
| *5 | Two 350MCM or larger | 2.5~4.5 |
|
|
|
|
| 6 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 7 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 8 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 9 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 10 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 11 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
| 12 | Two 250MCM or larger | 2.5~4.5 |
|
|
|
|
NOTE: Maximum cable size is 600MCM.
*Two battery strings or more (consult factory if using one battery string).
Table 11.7 Recommended Cable Size and Tightening Torque for 300kVA UPS.
| Bus Number | Cable Size | Torque to tighten |
| the terminal bus | ||
|
|
| |
|
|
|
|
| 1 | Two 4/0 AWG or larger | 2.5~4.5 |
|
|
|
|
| 2 | Two 4/0 AWG or larger | 2.5~4.5 |
| 3 | Two 4/0 AWG or larger | 2.5~4.5 |
| 4 | Three 350 MCM or larger | 2.5~4.5 |
|
|
|
|
| *5 | Three 350 MCM or larger | 2.5~4.5 |
|
|
|
|
| *6 | Two 4/0 AWG or larger | 2.5~4.5 |
| 7 | Two 4/0 AWG or larger | 2.5~4.5 |
| 8 | Two 4/0 AWG or larger | 2.5~4.5 |
| 9 | Two 4/0 AWG or larger | 2.5~4.5 |
|
|
|
|
| 10 | Two 4/0 AWG or larger | 2.5~4.5 |
| 11 | Two 4/0 AWG or larger | 2.5~4.5 |
| 12 | Two 4/0 AWG or larger | 2.5~4.5 |
NOTE: Maximum cable size is 600MCM.
*Two battery strings or more (consult factory if using one battery string).
32