Toshiba G8000 Series Recommended Cable Size and Tightening Torque for 125kVA UPS

Page 30

Table 11.2 Recommended Cable Size and Tightening Torque for 125kVA UPS.

Block Number

Cable Size

Tightening Torque

 

 

 

1

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

2

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

3

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

4

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

5

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

6

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

7

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

8

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

9

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

10

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

11

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

*12

Two 350MCM

3.2 kg-m (275 in-lbs)

 

 

 

*13

Two 350MCM

3.2 kg-m (275 in-lbs)

 

 

 

NOTE: Maximum cable size is 350MCM.

*One battery string (consult factory if using multiple battery strings).

Table 11.3 Recommended Cable Size and Tightening Torque for 150kVA UPS.

Block Number

Cable Size

Tightening Torque

 

 

 

1

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

 

 

 

2

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

3

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

4

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

5

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

6

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

7

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

8

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

9

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

10

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

11

AWG 4/0 or larger

3.2 kg-m (275 in-lbs)

*12

Two 350MCM or larger

3.2 kg-m (275 in-lbs)

 

 

 

*13

Two 350MCM or larger

3.2 kg-m (275 in-lbs)

 

 

 

NOTE: Maximum cable size is 350MCM.

*One battery string (consult factory if using multiple battery strings).

29

Image 30
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Keep the UPS room clean Do not install the UPS close to a water sourceKeep the specified clearance around the UPS Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Do not expose the UPS to water TransportationAvoid vibration or shock exceeding 0.5 G to the UPS Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundUnpacking Points to be observedUPS Clearance Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input