Table 11.2 Recommended Cable Size and Tightening Torque for 125kVA UPS.
Block Number | Cable Size | Tightening Torque |
|
|
|
1 | AWG 4/0 or larger | 3.2 |
|
|
|
2 | AWG 4/0 or larger | 3.2 |
|
|
|
3 | AWG 4/0 or larger | 3.2 |
|
|
|
4 | AWG 4/0 or larger | 3.2 |
|
|
|
5 | AWG 4/0 or larger | 3.2 |
|
|
|
6 | AWG 4/0 or larger | 3.2 |
|
|
|
7 | AWG 4/0 or larger | 3.2 |
|
|
|
8 | AWG 4/0 or larger | 3.2 |
|
|
|
9 | AWG 4/0 or larger | 3.2 |
|
|
|
10 | AWG 4/0 or larger | 3.2 |
|
|
|
11 | AWG 4/0 or larger | 3.2 |
|
|
|
*12 | Two 350MCM | 3.2 |
|
|
|
*13 | Two 350MCM | 3.2 |
|
|
|
NOTE: Maximum cable size is 350MCM.
*One battery string (consult factory if using multiple battery strings).
Table 11.3 Recommended Cable Size and Tightening Torque for 150kVA UPS.
Block Number | Cable Size | Tightening Torque |
|
|
|
1 | AWG 4/0 or larger | 3.2 |
|
|
|
2 | AWG 4/0 or larger | 3.2 |
3 | AWG 4/0 or larger | 3.2 |
4 | AWG 4/0 or larger | 3.2 |
5 | AWG 4/0 or larger | 3.2 |
6 | AWG 4/0 or larger | 3.2 |
7 | AWG 4/0 or larger | 3.2 |
8 | AWG 4/0 or larger | 3.2 |
9 | AWG 4/0 or larger | 3.2 |
10 | AWG 4/0 or larger | 3.2 |
11 | AWG 4/0 or larger | 3.2 |
*12 | Two 350MCM or larger | 3.2 |
|
|
|
*13 | Two 350MCM or larger | 3.2 |
|
|
|
NOTE: Maximum cable size is 350MCM.
*One battery string (consult factory if using multiple battery strings).