9. Storage

Observe following points when storing the UPS.

(1)Be sure to store UPS indoors.

(2)The best temperature at storing location is 20~25°C (68~77°F).

In case this temperature is difficult to be maintained, a temperature window of 0~40°C (32~104°F) should be observed. Temperature fluctuat ions should be minimal.

(3)Relative humidity at storing location should be 50~60%. Humidity must not exceed 90%.

(4)Avoid locations where corrosive gas is generated.

(5)Avoid dirty locations.

23

Image 24
Contents Document Number February Introduction Uninterruptible Power Supply Manual’s Purpose and Scope Contacting Toshiba’s Customer Support CenterGeneral Safety Instructions Important Safety Instructions Safety Precautions General Terms Do not remove the rear/side panels ProhibitedInstallation Precautions Avoid vibration or shock exceeding 0.5G to the UPSUPS Installation Environment Standard Keep the UPS room clean Do not install the UPS close to a water sourceKeep the specified clearance around the UPS Connect ground wire to the earth ground terminal only MandatoryLocations of the Warning Labels 100/125 kVA Locations of the Warning Labels 150/180/225 kVA AC Input Grounding Electrode Terminal Contents Dimensions and Weight 100/125kVA UPS Exterior dimensions front & right side150/180/225kVA UPS Exterior dimensions front & right side 250/300kVA UPS Exterior dimensions front & right side Transportation Avoid vibration or shock exceeding 0.5 G to the UPSDo not expose the UPS to water Transportation by a craneAngle more than Transportation by a forklift Storage Installation Ensure that there is adequate working space aroundUnpacking Points to be observedUPS Clearance Anchor bolts Anchor bolt tighteningExternal Wiring Diagram OverviewTerminal Blocks and Power Cables Phase 3-wire Phase 4-wireRecommended Cable Size and Tightening Torque for 125kVA UPS Recommended Cable Size and Tightening Torque for 180kVA UPS Phase 3-wire Phase 4-wire Recommended Cable Size and Tightening Torque for 250kVA UPS Ilsco External Breakers External Breaker RatingGrounding Wire 100~225kVA 250/300kVAControl Wires 10 External ConnectionsGrounding configuration Recommended configuration with input neutral groundedGrounding configuration without input neutral Recommended configuration with delta-inputGrounding configuration with corner-grounded delta-input 12 Grounding configuration with corner-grounded delta-input
Related manuals
Manual 63 pages 16.31 Kb